Product overview: Fluke 110 True-rms Digital Multimeter
Compact true-rms meter for accurate electrical installation and troubleshooting
The Fluke 110 is a versatile multimeter for electrical measurements and troubleshooting. Trusted by residential and commercial electricians for troubleshooting and maintenance. The 110 is for professional use, where true-rms accuracy is needed.
Key product capabilities
- True-rms ac voltage for accurate measurements on non-linear signals
- Large white LED backlight to work in poorly lit areas
- Resistance and continuity
- Min/Max/Average to record signal fluctuations
- CAT III 600 V safety rated
Specifications: Fluke 110 True-rms Digital Multimeter
Accuracy is specified for 1 year after calibration, at operating temperatures of 18 °C to 28 °C, with relative humidity at 0 % to 90 %. The accuracy specifications take the form of: ± ( [ % of Reading ] + [ Counts ] )
General specifications |
Maximum voltage (between any terminal and earth ground) |
600V |
Safety |
IEC 61010-1, Pollution degree 2
IEC 61010-2-033, CAT III 600 V |
Display |
Digital: 6,000 counts, updates 4/sec |
Bar graph |
33 segments, updates 32/sec |
Temperature
Operating
Storage |
-10 °C to + 50 °C
-40 °C to + 60 °C |
Battery |
9 volt Alkaline, IEC 6LR61 |
Battery life |
400 hours typical, without backlight |
Accuracy |
Measurement |
Range |
Resolution |
Accuracy ± ([% of reading] + [counts]) |
DC millivolts |
600.0 mV |
0.1 mV |
0.5 % + 2 |
DC volts |
6.000 V
60.00 V
600.0 V |
0.001 V
0.01 V
0.1 V |
0.5 % + 2 |
Accuracy |
Measurement |
Range |
Resolution |
Accuracy ± ([% of reading] + [counts]) |
AC millivolts1 true-rms |
600.0 mV |
0.1 mV |
1.0 % + 3 (dc, 45 Hz to 500 Hz)
2.0 % + 3 (500 Hz to 1 kHz) |
AC volts1 true-rms |
6.000 V
60.00 V
600.0 V |
0.001 V
0.01 V
0.1 V |
1.0 % + 3 (dc, 45 Hz to 500 Hz) 2.0 % + 3 (500 Hz to 1 kHz) |
Continuity |
600 Ω |
1 Ω |
Beeper on < 20 Ω, off> 250 Ω; detects opens or shorts of 500 μs or longer. |
Ohms |
600.0 Ω |
0.1 Ω |
0.9 % + 2 |
6.000 kΩ
60.00 kΩ
600.0 kΩ
6.000 MΩ |
0.001 kΩ
0.01 kΩ
0.1 kΩ
0.001 MΩ |
0.9 % + 1 |
40.00 MΩ |
0.01 MΩ |
5 % + 2 |
1All ac voltage ranges are specified from 1 % to 100% of range. Because inputs below 1 % of range are not specified, it is normal for this and other true-rms meters to display non-zero readings when the test leads are disconnected from a circuit or are shorted together. For volts, crest factor of ≤ 3 at 4000 counts, decreasing linearly to 1.5 at full scale. AC volts is ac-coupled.
Compatible accessories: Fluke 110 True-rms Digital Multimeter
Cases and holsters (7)
Fluke C50 Meter Case
Fluke CXT170 Extreme Case
Fluke C25 Large Soft Case for DMMs
Fluke TPAK ToolPak™ Magnetic Meter Hanger
Fluke C35 Soft Carrying Case
Fluke C11XT Protective EVA Hard Tool Case
Fluke C37XT Protective EVA Hard Tool Case
Test leads, probes and clips (13)
Fluke TL220 SureGrip™ Industrial Test Lead Set
Fluke AC285 SureGrip™ Alligator Clips
Fluke AC87 Heavy Duty Bus Bar Clip Set
Fluke TL223 SureGrip™ Electrical Test Lead Set
Fluke TL71 Premium Test Lead Set
Fluke TL175 TwistGuard™ Test Leads
Fluke TL75 Hard Point™ Test Lead Set
Fluke TL224 SureGrip™ Insulated Test Leads
Fluke TLK-225 SureGrip™ Master Accessory Set
Fluke TP175 TwistGuard™ Test Probes
Fluke TP220 SureGrip™ Industrial Test Probes
Fluke TP1 Slim Reach Test Probes
Fluke TL175-HV CAT III 1500 V TwistGuard™ Test Leads
Lights (2)
Fluke LVD1A Non-Contact Voltage Tester with LED Flashlight
Fluke L206 Deluxe LED Hat Light
Current clamps and probes (1)
Fluke i1010 AC/DC Current Clamp
Thermometer (1)
Fluke 80TK Thermocouple Module