Omron CS1W-AD081-V1 I/O Unit Malaysia

Omron CS1W-AD081-V1 I/O Unit Malaysia

Category: OMRON PLC Available
For more information, visit our official website at sjtsuccess.com.my

Description

Item CS1W-AD041-V1 CS1W-AD081-V1 CS1W-AD161
Applicable PLC model CS series
Unit type CS1 Special I/O Unit
Isolation *1 Between I/O and PLC signals: Photocoupler
(No isolation between individual I/O signals.)
External terminals 21-point detachable terminal block
(M3 screws)
Two 34-pin MIL connectors
Affect on CPU Unit cycle time 0.2 ms
Power consumption 120 mA max. at 5 VDC,
90 mA max. at 26 VDC
150 mA max. at 5 VDC,
55 mA max. at 26 VDC
Dimensions (mm) *2 35 × 130 × 126 (W × H × D) 35 × 130 × 119 (W × H × D)
Weight 450 g max.
General specifications Conforms to general specifications for SYSMAC CS Series.
Mounting position CS-series CPU Rack or CS-series Expansion Rack
(Cannot be mounted to a C200H Expansion I/O Rack or a SYSMAC BUS Slave Rack.)
Maximum number of Units Depends on the power supply Unit. *3
Data exchange with CPU Units *4 Special I/O Unit Area in CIO Area (CIO 2000
to CIO 2959): 10 words per Unit
Special I/O Unit Area in DM Area (D20000
to D29599): 100 words per Unit
Special I/O Unit Area in CIO Area
(CIO 2000 to CIO 2959): 20 words per Unit
Special I/O Unit Area in DM Area
(D20000 to D29599): 200 words per Unit
Input
specifications
Number of analog
inputs
4 8 16
Input signal range *5 1 to 5 V
0 to 5 V
0 to 10 V
- 10 to 10 V
4 to 20 mA
*6
Maximum rated input
(for 1 point) *7
Voltage Input: ± 15 V
Current Input: ± 30 mA
Input impedance Voltage Input: 1 M Ω min.
Current Input: 250 Ω (rated value)
Resolution 4,000/8,000 *8
Converted output data 16-bit binary data
Accuracy
*9
23 ± 2 °C Voltage Input: ± 0.2% of full scale
Current Input: ± 0.4% of full scale
Voltage Input: ± 0.2% of full scale
Current Input: ± 0.2% of full scale
0 °C to
55 °C
Voltage Input: ± 0.4% of full scale
Current Input: ± 0.6% of full scale
Voltage Input: ± 0.4% of full scale
Current Input: ± 0.4% of full scale
A/D conversion time
*10
1.0 ms or 250 μs per point max. *8
Mean value processing Stores the last ''n'' data conversions in the buffer, and stores the mean value of the conversion values.
Buffer number: n = 2, 4, 8, 16, 32, 64
Peak value holding Stores the maximum conversion value while the Peak Value Hold Bit is ON.
Input disconnection
detection
Detects the disconnection and turns ON the Disconnection Detection Flag. *11
Scaling function None None Enabled only for conversion time of 1 ms
and resolution of 4,000. Setting any
values within a range of ± 32,000 as the
upper and lower limits allows the A/D
conversion result to be output with
these values as full scale.