Power supply circuit | ||
Through an external power supply unit | 100...240 V ac / 12 V dc | |
Frequency | 50...60 Hz | |
Consumption | 15 V·A | |
Operating temperature | 0...+40 ºC | |
Altitude | ≤ 2 000 m | |
Humidity of operation | 80 % for temperatures under 31 ºC, with a linear decrease down to 50 % at 40 ºC | |
Metering circuit | Three-phase (3 wires) | Three-phase (3 / 4 wires) |
Voltage circuit | ||
Measurement range | In accordance with the clamp, 0.01 A...20 kA | |
Voltage and current transformation ratios | Programmable | |
Measurement units | Automatic change of scale | |
Internal memory | 1 Mb | |
Accuracy class (*) | ||
Voltage | 0.5 % ± 2 digits | |
Current | 0.5 % ± 2 digits | |
Active power | 1 % ± 2 digits | |
Power factor | 1 % ± 2 digits | |
Build features(*) | ||
Housing | Reinforced insulation | |
Keyboard / Display | On the front panel | |
Display | LCD 160 x 160 pixels (backlit) | |
Current clamp connector | 3 | 3 / 4 |
Dimensions | 220 x 60 x 130 mm | |
Weight | 800 g | |
RS-232 Outputs | Series output | |
Safety | Category III - 600 V, in accordance with 61010 |
Standards | ||
EN 61000-3-2 (1995), Harmonics | ||
EN 61000-3-3 (1995), Voltage fluctuations | ||
EN 61000-6-4 (2002), Industrial emissions EN 55011 (1994), Driven (EN 52022 – Class B) EN 55011 (1994), Radiated (EN 55022 – Class A) |
||
EN 61000-6-2 (2022), Industrial immunity EN 61000-4-2 (1995), Electrostatic discharge ENV 50140 (1993), Radiated electromagnetic field EN 61000-4-8 (1995), Rapid transient bursts ENV 50141 (1993), RF in common mode EN 61000-4-8 (1995), Magnetic field at 50 Hz |
||
EN 61000-6-1 (2002), Domestic immunity EN 61000-4-5 (1995), Shockwave EN 61000-4-11 (1994), Power supply interruptions |
||
(*) Accuracy is given by the following measurement conditions: Exclusion of errors produced by the clamps and external voltage transformers, with a range of temperature of 5 ... 45 ºC and power factor of 0 ... 1 |