详情
The equipment called NEVERS allows to the operator to ground and to short circuit the overhead lines up to 11 m heights without using rifters or without climbing on poles and pylon. The equipment allows moreover the operator to check the presence/absence of tension on overhead conductors up to 11 m fitting the voltage detector on the lowest element of the telescopic rod
Equipment contents
-
3 Light alloy auto-blocking contact clamp type PC-AB with automatic clamping of conductor in case of short circuit. Clamping capacity: round conductors Ø 3÷22 mm.
-
3 Insulating telescopic rods in 4 elements in aluminum with attack for voltage detector (not included) on the lower element. Extended length 6.60 m, folded length 1.86 m.
-
High insulating rod type PVR3/495/FOR in vinylester resin tube reinforced by fiberglass, diameter Ø 40 mm, filled by closed cells polyurethane foam, certified in conformity with IEC 60855-1. Total length 4.95 m in 3 elements length 1,65 m each.
-
Extraflexible electrolytic copper cables covered by transparent plastic sheath, section 35 mm2, length 10 m (other lengths on demand).
-
2 hexagonal CH18 earth rod type 6041.00.
-
Rod lifting system to install it on one of the two earth rods, type WI/DSF.
-
Rotating cable coiler with earth clamp to install on the other earth rods type WI/BARM.
-
Heavy fabric bag for the transport of the aluminium and insulating rods, earth rods and lifting system.
更多 United Integration Technology Sdn Bhd 相关资料