FLUKE - 381 Remote Display True RMS AC/DC Clamp Meter with iFlex®
Brand: Fluke
Model: Fluke 381
Key Features:
Wireless technology allows the display to be carried up to 30 ft. away from the point of measurement for added flexibility without interference with measurement accuracy
The removable magnetic display can be conveniently mounted where it is easily seen
iFlex® Flexible Current Probe expands the measurement range to 2500 A AC
CAT IV 600 V, CAT III 1000 V
Integrated low pass filter and state-of-the-art signal processing allows for use in noisy electrical environments while providing stable readings
Proprietary inrush measurement technology to filter out noise and capture motor starting current exactly as the circuit protection sees it
Ergonomic design fits in your hand and can be used while wearing protective equipment
Radio transmitter automatically sets the correct measurement range so you do not need to change the switch positions while taking a measurement
Three-year warranty
Soft carrying case
Safety Conformance:
IEC/EN 61010-1:2001, 1000V CAT III, 600V CAT IV
Specifications:
Electrical Specifications |
||||
AC Current via Jaw |
||||
Range |
999.9 A |
|||
Resolution |
0.1 A |
|||
Accuracy |
2% ± 5 digits (10-100 Hz) |
|||
Crest Factor (50/60 Hz) |
3 @ 500 A |
|||
AC Current via Flexible Current Probe |
||||
Range |
999.9 A / 2500 A (45 Hz – 500 Hz) |
|||
Resolution |
0.1 A / 1 A |
|||
Accuracy |
3% ± 5 digits |
|||
Crest Factor (50/60 Hz) |
3.0 at 1100 A |
|||
Position Sensitivity |
||||
|
Distance from Optimum |
|||
|
i2500-10 Flex |
i2500-18 Flex |
Error |
|
A |
0.5 in (12.7 mm) |
1.4 in (35.6 mm) |
±0.5% |
|
B |
0.8 in (20.3 mm) |
2.0 in (50.8 mm) |
±1.0% |
|
C |
1.4 in (35.6 mm) |
2.5 in (63.5 mm) |
±2.0% |
|
Measurement uncertainty assumes centralized primary conductor at optimum position, no external electrical or magnetic field, and within operating temperature range. |
||||
DC Current |
||||
Range |
999.9 A |
|||
Resolution |
0.1 A |
|||
Accuracy |
2% ± 5 digits |
|||
AC Voltage |
||||
Range |
600 V /1000 V |
|||
Resolution |
0.1 V / 1 V |
|||
Accuracy |
1.5% ± 5 digits (20 – 500 Hz) |
|||
DC Voltage |
||||
Range |
600.0 V /1000 V |
|||
Resolution |
0.1 V / 1 V |
|||
Accuracy |
1% ± 5 digits |
|||
Frequency – Via Jaw |
||||
Range |
5.0 – 500.0 Hz |
|||
Resolution |
0.1 Hz |
|||
Accuracy |
0.5% ± 5 digits |
|||
Trigger Level |
5 – 10 Hz, ≥ 10 A |
|||
Frequency via Flexible Current Probe |
||||
Range |
5.0 to 500.0 Hz |
|||
Resolution |
0.1 Hz |
|||
Accuracy |
0.5% ± 5 digits |
|||
Trigger Level |
5 to 20 Hz, ≥ 25 A |
|||
Resistance |
||||
Range |
600 Ω/6 kΩ/60 kΩ |
|||
Resolution |
0.1 Ω/1 Ω/10 Ω |
|||
Accuracy |
1% ± 5 digits |
|||
Mechanical Specifications |
||||
Size (L x W x H) |
277 x 88 x 43 mm (55 mm for remote unit) |
|||
Weight |
350 g |
|||
Jaw Opening |
34 mm |
|||
Flexible Current Probe Diameter |
7.5 mm |
|||
Flexible Current Probe Cable Length |
1.8 m |
|||
Environmental Specifications |
||||
Operating Temperature |
-10°C to +50°C |
|||
Storage Temperature |
-40°C to +60°C |
|||
Operating Humidity |
Non condensing (< 10°C) |
|||
Operating Altitude |
2,000 meters |
|||
Storage Altitude |
12,000 meters |
|||
EMI, RFI, EMC, RF |
EN 61326-1:2006, EN 61326-2-2:2006 |
|||
Temperature Coefficients |
Add 0.1 x specified accuracy for each degree C above 28°C or below 18°C |
|||
Wireless Frequency |
2.4 GHz ISM Band 10 meter range |
|||
Safety Compliance |
ANSI/ISA S82.02.01:2004 |
|||
Double Insulation Clearance |
Per IEC 61010-2-032 |
|||
Double Insulation Creepage |
Per IEC 61010-1 |