Cycling Capacity
20 hour rate: 245 Amp Hours
|
Reserve Capacity
@ 25 Amps: 457 minutes
@ 75 Amps: 120 minutes
|
Mechanical Specifications
Group Size: DIN
Terminal Type: AP
Total Height: 10.83″ (275 mm)
Height: 10.83″ (275 mm)
Width: 7.48″ (190 mm)
Length: 9.61″ (244 mm)
Weight: 72.8 lbs (33 kg)
Case Type: ABS Plastic – Flame Res Rating UL94-HB
|
Electrical Specifications
Nominal Voltage: 6 Volt
Capacity @ 100 hour rate: 270 AH
Capacity @ 20 hour rate: 245 AH
Capacity @ 10 hour rate: 221 AH
Capacity @ 5 hour rate: 198 AH
CCA: 930 Amps
CA or MCA: 1120 Amps
PHCA: 2000 Amps
Short Circuit Current: 3210 Amps
Internal Resistance: 1.4m Ω
|
Time | Amps | Rate |
20 hr | 12.3 | 0.05 CA |
10 hr | 22.1 | 0.1 CA |
8 hr | 24.9 | 0.13 CA |
5 hr | 39.6 | 0.25 CA |
3 hr | 55.4 | 0.33 CA |
2 hr | 74.9 | 0.5 CA |
1 hr | 137 | 1 CA |
Charge Stage | Battery Voltages-12V | Battery Voltages-24V | Battery Voltages-36V | Battery Voltages-48V |
Bulk | 14.7 V | 29.4 V | 44.1 V | 58.8 V |
Absortion | 14.7 V | 29.4 V | 44.1 V | 58.8 V |
Float | 13.6 V | 27.2 V | 40.8 V | 54.6 V |
TC Factor: -4mV/°C/cell |
Temperature Range Specifications
Condition | Recommended | Maximum |
Storage | -15°C to 50°C | -40°C to 71°C |
Operation | -15°C to 40°C | -40°C to 71°C |
Charge with TC | -15°C to 50°C | -40°C to 71°C |
Charge without TC | 0°C to 40°C | -15°C to 50°C |
Terminal Type | ft-lbs | in-lbs | Nm |
AP | DT (AP) | M6 | M6M (stud) | TP07 (AP) | TP08 (AP) | 4.2 – 6.0 | 50 – 70 | 5.6 – 7.9 |
FR45 | 6.0 – 7.5 | 70 – 90 | 7.9 – 10.1 |
M8 | 7.1 – 8.0 | 85 – 95 | 9.6 – 10.7 |
DT (stud) | M10M (stud) | 9.2 – 10.4 | 110 – 125 | 12.2 – 14.0 |