Test voltage | 250V/500V/1000V |
---|---|
Measuring ranges (Mid-scale value) |
20MΩ/200MΩ/2000MΩ |
Output voltage on open circuit | Rated test voltage+20%, -0% |
Nominal current | 1mA DC min. |
Output short circuit current | 1.5 mA DC approx. |
Accuracy |
±1.5%rdg±5dgt (20MΩ/200MΩ) ±10%rdg±3dgt (2000MΩ) |
Measuring ranges (Mid-scale value) |
20Ω/200Ω/2000Ω |
---|---|
Output voltage on open circuit | 7 - 12V DC |
Measuring current | 200mA DC min. |
Accuracy |
±1.5%rdg±5dgt (20Ω) ±1.5%rdg±3dgt (200Ω/2000Ω) |
AC voltage range | 0-600V AC |
---|---|
Accuracy | ±5%rdg±3dgt |
Safety Standard |
IEC 61010-1 CAT III 300V Pollution Degree 2 IEC 61010-2-031 IEC 61557-1/2/4 |
---|---|
IP Rating | IEC 60529-IP54 |
EMC Standard | IEC 61326-1 |
Power source | R6 (AA) (1.5V) × 8 |
Dimensions | 167(L) × 185(W) × 89(D)mm |
Weight | 990g approx |
Included Accessories |
7122B (Test leads) Pouch for test leads 8923 (F500mA/600V fuse) × 2 R6 (AA) × 8 Shoulder Strap Instruction Manual |