详情



• High-speed input models are available, meeting versatile applications. ON Response Time: 15μs, OFF Response Time: 90μs
• Use 24-VDC, 100-VAC, and 200-VAC models to connect to devices with different types of outputs.
• The 24-VDC models can be connected to devices with either NPN or PNP outputs. There is no need to select the polarity.
• A digital filter in the Unit can be set from 0 to 32 ms to reduce the influence of external noise.
• Either a Fujitsu or MIL connector interface can be used.
• Several models of Terminal Block Conversion Units are available, making it easy to connect to external devices.
Model CJ1W-OD261
Rated Voltage 12 to 24 VDC
Operating Load
Voltage Range 10.2 to 26.4 VDC
Maximum Load
Current 0.3 A/point, 1.6 A/common, 6.4 A/Unit
Maximum Inrush
Current 3.0 A/point, 10 ms max.
Leakage Current 0.1 mA max.
Residual Voltage 1.5 V max.
ON Response
Time 0.5 ms max.
OFF Response
Time 1.0 ms max.
Insulation
Resistance 20 MΩ between the external terminals and the GR terminal (100 VDC)
Dielectric
Strength 1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of
10 mA max.
Number of
Circuits 64 (16 points/common, 4 circuits)
Internal Current
Consumption 5 VDC, 170 mA max.
Fuse None
External Power
Supply 10.2 to 26.4 VDC, 50 mA min.
Weight 110 g max