Butane / Isobutane Sensor and Monitoring System
Benefits
-
Protects life, property and company profits
-
Ideal for remote locations
-
Fail safe mode in event of loss of power
-
Up to three (3) sensors can be installed to main control to meet space coverage requirements
Features
-
Universal power inputs: 110/220 Vac and/or 12–48 Vdc input
-
Strobe light for visual alerts
-
Sensor status indicator LEDs on the main control
-
Modular design for optimal placement of sensor(s)
Installation
-
Wall or 2-gang junction box mountable
-
Mechanical relays are easily accessible:
-
Warning 25% relay, 15 A @ 120 Vac; 10 A @ 277 Vac; 10 A @ 28 Vdc
-
Alarm 50% relay, 0.5 A resistive @ 28 Vdc, 0.5 A @ 125 Vac
-
Redundant power supply capability; dual AC and/or DC power supply connections (DC power supply will operate as backup power source)
-
Indicator LEDs can be tested by pushing the red “TEST” button
-
Sensors can be tested in the field with the P/N C4H10-TESTKIT
Detector can operate exhaust fans and building alarms / SCADA systems:
Warning Settings: Should the concentration of butane / isobutane gas in the air surrounding the sensor reach 25%LEL by volume, the “25%LEL Warning” yellow LED will light up on the main control of the unit. In addition, the 25%LEL internal relay will energize and can be used to activate an external exhaust fan.
Alarm Settings: Should the butane / isobutane gas concentration reach 50%LEL by volume, the “50% Alarm” red LED will light up, the strobe will flash and an audible alarm will sound. In addition, the 50%LEL internal relay will energize and can be used to activate a building management/alarm system (via SCADA/Modbus).
SBS-C4H10 Includes
-
Main unit
-
Butane / Isobutane sensor
-
25 ft. cable
Specification
Power Supply(s) |
110/220 Vac, 50/60 Hz and/or
12–48 Vdc (9–58 Vdc operating voltage) |
50% LEL (Lower Explosive Limit) |
Dry contacts rated 0.5A/28 Vdc |
Dimensions |
4.7'' L x 4.7'' W x 1.2'' D (main control) |