Technical data | EL3102 |
---|---|
Number of inputs | 2 (differential) |
Power supply | via the E-bus |
Signal voltage | -10…+10 V |
Oversampling factor | – |
Input signal bandwidth | – |
Distributed clocks | yes |
Distributed clock precision | << 1 µs |
Internal resistance | > 200 kΩ |
Input filter limit frequency | 5 kHz |
Common-mode voltage UCM | max. 35 V (relative to the internal GND) |
Conversion time | ~ 60 µs (fast mode ~ 40 µs) |
Resolution | 16 bit (incl. sign) |
Measurement error/ uncertainty | < ±0.3% (relative to full scale value) |
Electrical isolation | 500 V (E-bus/signal voltage) |
Current consumption power contacts | – |
Current consumption E-bus | typ. 170 mA |
Bit width in the process image | inputs: 8 byte |
Special features | standard and compact process image, switchable measuring data representation, activatable FIR/IIR filters, limit value monitoring |
Operating/storage temperature | -25…+60°C/-40…+85°C |
Weight | approx. 60 g |
Relative humidity | 95%, no condensation |
Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. rating/installation pos. | IP20/variable |
Approvals/markings | CE, UL, ATEX, IECEx |
Pluggable wiring | for all ESxxxx terminals |
Ex marking |
ATEX: II 3 G Ex ec IIC T4 Gc IECEx: Ex ec IIC T4 Gc |