AWAX 27XXL - DOUBLE SAFETY RELAY - DOUBLE SELF-CHECK BOX
Sensor controller on Acotom process / mechanical switches / emergency stops
Safety management in 2 zones in a compact 45 mm format
Short-circuit detection in 2 µs, self-resetting
Removable terminals
Performance level with AWAX controller: PL = e
Safety category: 4
Safety Integrity Level: SIL 3
Time before dangerous failure: MTTFd = 415 years
Cycle before dangerous failure: B10d=100,000 at 5A
Risk duration: 20 ms max.
Cable severing protection: yes (opening of safety lines)
Short-circuit and overload protection: yes, using DLC (opening of safety lines and current limiting in contacts)
Reaction 2 µs ultrafast
Safety contacts/diagnostics zone 1: 3x NO 8A/250V redundant / 1x NF 8A/250V redundant series
Safety contacts/diagnostics zone 2: 3x NO 8A/250V redundant / 1x NF 8A/250V redundant series
Indicators: 2 display LEDs per zone for diagnostics and 1 LED for power
Reset: configurable by dip-switch (SR=Automatic, N=manual)
Mounting: symmetrical DIN 35mm rail on DIN 50022
Mounting: IP 54 electrical box
Electrical connection: Maximum 14 AWG (2.08 mm²) / 250V minimum
Temperature: -20°C to +60°C
Certification: TÜV Rheinland 01/205/5168/11