Three Phase Network and Quality Analyzers
This analyzer is the most complete of the latest generation of portable analyzers. It has a colour graphic display screen with high resolution that allows you to see graphics in detail.
The AR6 Analyzer has 5 inputs for measuring voltage and 5 inputs for measuring currents for each phase and neutral. The other input allows for measurement of the leakage current simultaneously.
The power analyzer allows the user to measure and record power quality parameters (overvoltage, cuts and gaps) that are configured in a particular menu, in addition to recording wave shapes, flicker, energy and all measured parameters therein.
It has quadrant display per phase that lets you know how it is working in each measured line, detects imbalances, and sees lags between voltages and currents. All of this with its powerful graphics processor, along with its high resolution screen, makes this analyzer a very visual tool.
The AR6 Analyzer simultaneously records all network parameters and includes powerful analysis tools, combined with PowerVision PLUS, making it the perfect interface between installations in need of optimisation and their energy audits.
With the AR6 you can perform a full study of the electrical installation. It is possible to perform an analysis of consumption, load curves, voltage disturbances in the installation and to display waveshapes, study harmonics or measure flicker, as well as other options.
AR6 | ||
Class 0.5 in the measurement Class B according to UNE-EN 61000-4-30 Measurement and recording according to EN 50160 |
||
AR6 power supply | ||
Voltage (external power supply) | 100…240 Vac. | |
Current (external power supply) | 3.33 A | |
Frequency | 50 to 60 Hz | |
Maximum power | 40 W | |
AR6 | ||
Nominal voltage | 12 Vdc | |
Current | 2 A | |
Maximum power | 24 W | |
Consumption | 30 VA | |
Operating temperature | 0 to 50ºC | |
Altitude | 2000 m | |
Humidity without condensation | 5…95 % | |
Contamination level | 2 | |
Current input features | ||
Current inputs | I1 , I2 , I3 , IN , Lleakage | |
Input voltage | 0…2 V | |
Measurement margin | 1 to 120 of In% | |
Maximum current | 3In A | |
Input impedance | 10 kΩ | |
Voltage input features | ||
Voltage inputs | U1, U2, U3, UN, Earthing | |
Input voltage | 10 to 800 Vrms neutral phase | |
Maximum voltage admissible | 2,500 V | |
Bandwidth | 3.2 kHz | |
Other features | ||
Voltage measurement range | 10 to 800 Vf-n | |
Current measurement range | 0.01 to 1000 A (depending on clamp) | |
Transformation ratios | Programmable | |
Internal memory | 1 Gb | |
Internal memory features | FAT 32 | |
Accuracy class | ||
Voltage | 0.5% ± 2 digits | |
Current | 0.5% ± 2 digits | |
Active power | 1% ± 2 digits | |
Reactive power | 1% ± 2 digits | |
Build features | ||
Enclosure | Double insulation | |
Keyboard | Movement and function keys | |
Screen | 5.7“ colour VGA | |
Dimensions | 283 x 168 x 80 mm | |
Weight | 1.640 kg | |
Communications | USB | |
Safety | Category III - 600 V, in accordance with 61010 1000 V CAT III/600 V CAT IV for altitudes lower than 2000 m 1000 V CAT III/600 V CAT III/300 V CAT IV above 2000 m |
|
Standards | ||
EN 61000-6-4 (2002), Industrial emissions. EN 55011 (1994), Driven (EN 52022 – Class B) EN 55011 (1994), Radiated (EN 55022 – Class A) |
||
EN 61000-6-2 (2022), Industrial immunity EN 61000-4-2 (1995), Electrostatic discharge EN 61000-4-8 (1995), Rapid transient bursts |
||
EN 61000-6-1 (2002), Domestic immunity EN 61000-4-11 (1994), Power supply outages |
||
(*) Accuracy is given by the following measurement conditions: Exclusion of errors produced by the clamps and external voltage transformers, with a temperature range of 5 to 45ºC and power factor 0 to 1 |
Portable power analyzer for three-phase and single-phase electrical networks with simultaneous measurement of leakage current, power quality and recording of transients.
AR6 is the best tool for visualizing and analyzing the network’s problems regardless of whether it is a single-phase or three-phase network.
It allows recordings of the most common electrical parameters and also those specifically related to supply quality such as overvoltages, swell, sags and transients.
Thanks to the graphical display of harmonics, phasors and waveforms, the user can detect anomalies in the installation simply by connecting the device.
Measurement of the main electrical parameters.
True root mean square measure (TRMS).
5.7” colour graphic screen.
Includes meter for energy consumed and generated.
Has 5 voltage measurement inputs and 5 current channels.
Configurable trigger menu via level and time trigger.
Multiple languages (Spanish, English, French, German, Portuguese, Italian, Chinese, Russian).
Recording of voltage-quality events (class B) via configurable menu.
600 CAT IV, 1000V CAT III (EN 61010).
CE marking.
Analysis of records via Power Vision plus PC software.
Simple and intuitive menu for device configuration.
List of detected disturbances in tables.
Display of wave shapes of transients recorded.
Manual or programmed PHOTO captures (wave shapes of 9 channels along with instantaneous values).
Compatible with AR5-L pins.
Automatic detection of clamps.
Memory download via USB connection.
Graphic display of phasors, harmonics and wave shapes.