INPUT TECHNICAL DATA |
|
Input rated voltage |
120–230 Vac |
Input voltage AC |
85…264 Vac |
Input voltage DC |
100…370 Vdc (derating Uin |
Frequency |
47…63 Hz |
Current consumption |
4.9 A (120 Vac) / 2.4 A (230 Vac) |
Inrush peak current |
36 A |
Power factor |
> 0.99 |
Internal protection fuse |
Yes 8 A |
External protection on AC line |
MT: C-6 A / Fuse: T-6.3 A |
OUTPUT TECHNICAL DATA |
|
Output voltage range |
24 Vdc ±1% |
Output adjustable range |
21 … 29 Vdc |
Continuous current |
20 A at 50°C |
Overload limiting |
23 A (max. 25 A constant current) |
Short circuit peak current |
32 A 300 ms On /800 ms Off (HICCUP mode) |
Ripple @ nominal ratings |
200 mVpp |
Hold up time |
18 ms (120 Vac) / 18 ms (230 Vac) |
Status indication |
LED ''DC OK'', LED ''Stand-by'' |
Alarm contact |
dry contact, max. 1A |
Parallel connection |
possible |
Redundant parallel connection |
possible with external ORing diode |