Our compact insulation meter is perfect for measuring the insulation resistance of electrical appliances and household appliances. With its ability to measure insulation resistance, AC voltage, low resistance, PI (polarization index) and DAR (dielectric absorption), it is a versatile and reliable tool for many application scenarios. With test voltages of 100 V, 250 V, 500 V and 1000 V, insulation resistances up to 5.5 GΩ can be measured, allowing for accurate analysis and evaluation of insulation quality. The insulation meter not only provides the ability to measure direct current (DC) in the measurement range from 30 V to 600 V and alternating voltage (AC), but also detects resistance in the range of 0 Ω to 999 Ω with high accuracy to ensure good diagnosis of electrical systems.
The automatic AC and DC detection as well as the automatic discharge guarantee user-friendly operation and maximum safety during the measurement process. In addition, the insulation meter has a high-voltage alarm and an alarm when limit values are exceeded to inform the operator of possible risks. The insulation meter is powered by 6 x AA batteries and also has the option of an external power supply of 9V DC.Then device complies with the standards: CAT III 600 V, CAT I 2500 V and IEC 6010-1, and is supplied with approx. 80 cm long test leads in a device bag.
Highlight
DC Voltage DC | |
Measuring range | 30 V ... 600 V |
Resolution | 1 V |
Accuracy | ±2% v.Mw. ±3 digits |
AC Voltage AC | |
Measuring range | 30 V ... 600 V |
Resolution | 1V |
Accuracy | ±2% v.Mw. ±3 digits |
Overload | AC 720 V / 10 seconds |
Insulation resistance | |
Test voltage DC | 100 V |
Measuring range | 0 GΩ ... 1.5 GΩ |
Resolution | 0.01 GΩ |
Accuracy | ±5% v.Mw. ±3 digits (over 100 kΩ) |
Insulation resistance | |
Test voltage DC | 250 V |
Measuring range | 0 GΩ ... 5.5 GΩ |
Resolution | 0.01 GΩ |
Accuracy | ±5% v.Mw. ±3 digits (over 100 kΩ) |
Insulation resistance | |
Test voltage DC | 500 V |
Measuring range | 0 GΩ ... 5.5 GΩ |
Resolution | 0.01 GΩ |
Accuracy | ±5% v.Mw. ±3 digits (over 100 kΩ) |
Insulation resistance | |
Test voltage DC | 1000 V |
Measuring range | 0 GΩ ... 5.5 GΩ |
Resolution | 0.01 GΩ |
Accuracy | ±5% v.Mw. ±3 digits (over 100 kΩ) |
Resistance | |
Measuring range | 0 Ω ... 999 Ω |
Resolution | 0,1 Ω |
Accuracy | ±(2% v.Mw +3 digits) |
General technical data | |
Measurement Functions | HOLD, PI, DAR |
Display Type | LC color display |
Measurement Rate | 2 Hz |
Standard(s) | IEC 6010-1 |
Life | 12 h |
Safety standard | CAT III 600 V, CAT I 2500 V |
Alarm | optical, acoustic |
Language | English |
Protection class (device) | IP20 |
Power supply | DC9V |
Weight | 689 g |
Dimensions (L x W x H) | 110 x 176 x 77 mm |
Service conditions | 0 ... 40 °C , 0 ... 85 % RH |
Storage | -20 ... 60 °C , 0 ... 90 % RH |
Battery/Battery | 6x 1.5 V AA battery, alkaline manganese |
Capacity | 3000 mAh |