High overload capability to ensure the protections selectivity and start-up of heavy loads
Series |
Universal Power |
Code |
XCSW121C |
Type |
CSW121C |
HS code |
85044083 |
INPUT TECHNICAL DATA |
|
Input rated voltage |
1-2x 230-400-500 Vac |
Input voltage AC |
187…550 Vac |
Input voltage DC |
270…725 Vdc |
Frequency |
47…63 Hz |
Current consumption |
1.1 A (230 Vac) / 0.55 A (400 Vac) |
Inrush peak current |
20 A |
Power factor |
> 0.65 |
External protection on AC line |
MT: C-6 A / Fuse: T-4 A |
OUTPUT TECHNICAL DATA |
|
Output voltage range |
24 Vdc ±1% |
Output adjustable range |
24…27.5 Vdc |
Continuous current |
5 A |
Overload limiting |
7.5 A for >30 s |
Short circuit peak current |
14 A for 0.4 s |
Ripple @ nominal ratings |
100 mVpp |
Hold up time |
20 ms (230 Vac) / 80 ms (400 Vac) |
Status indication |
LED ''DC OK'' / LED ''Alarm'' |
Alarm contact |
dry contact, max. 1A |
Parallel connection |
possible |
Redundant parallel connection |
possible with external ORing diode |
GENERAL TECHNICAL DATA |
|
Efficiency |
87% (230 Vac) / 87% (400 Vac) |
Dissipated power |
18 W (230 Vac) / 18 W (400 Vac) |
Operating temperature range |
–20…+60°C (derating -3 W >45°C) |
Input / output isolation |
3 KVac / 60 s (SELV output) |
Input / ground isolation |
1.5 kVac / 60 s |
Output / ground isolation |
0.5 kVac / 60 s |
Standard / approvals |
EN 60950-1 |
EMC Standard |
EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4 |
Overvoltage category / pollution degree |
II / 2 |
Protection degree |
IP 20 |
Connection terminal |
2.5 mm² / 2.5 mm² |
Housing material |
aluminium |
Dimensions (LxHxD) |
40x130x115 mm |
Approximate weight |
600 g |
Mounting information |
vertical on a rail, 10 mm from adjacent components |
ACCESSORIES |
|
Mounting rail (IEC60715/TH35-7.5) |
PR/3/AC, PR/3/AC/ZB, PR/3/AS, PR/3/AS/ZB |
Mounting rail (IEC60715/TH35-15) |
PR/3/PP, PR/3/PP/ZB, PR/3/PA, PR/3/PA/ZB |
APPROVALS AND MARKINGS |
|