Wireless Pro-F Sensor WS-THMDOF-C-902

Wireless Pro-F Sensor WS-THMDOF-C-902

Kategorya: Carrier Magagamit
Para sa karagdagang impormasyon, bisitahin ang aming opisyal na website sa unitedfaith.com.my

Deskripsyon

As part of Carrier’s wireless sensing line, wireless Pro-F sensors are used to measure temperature, humidity and occupancy in a space. Because there are no wires to run, they can be added to your building easily.

Wireless sensors work in conjunction with a wireless adapter, which enables wireless communication between the sensors and an i-Vu® BACnet controller in the space. By sensing temperature, humidity and occupancy wirelessly, our i-Vu controllers can make smart decisions to optimize the control of heating, cooling, and lighting systems in the building, providing optimum occupant comfort and energy efficiency.
 

Product Features

Comprehensive Capabilities

  • Wireless and battery-less space sensors (assuming sufficient lighting exists in space)
  • Maintenance-free capacitors power the sensors during unlit periods for up to 4-days without a light source
  • No repeaters or amplifiers required for zone-based applications
  • Can co-exist on Rnet with Carrier’s wired ZS sensors
  • Single-zone controllers can support a total of 5 sensors
  • Multi-zone controllers can support up to 15 sensors
Power supply Solar harvesting, internal energy storage
Supplemental battery Two SAFT LS-14500 AA 3.6V batteries. Not user replaceable. Under normal conditions, life expectancy is 5 to 10 years
Maximum operating life Up to 4 days with no light power or battery
Time to fully charge Depends on available lux. Full charge in 8 hours @ 1000 lux or 24 hours @333 lux
Temperature sensor measuring range 32° to 104°F (0° to 40°C)
Humidity sensor 0% to 100%, ±3% RH typical 5% drift per year
Motion sensor Panasonic AMN42122 - Effective detection range: 16.4 ft. (5 m) maximum
Protocol Customized version of EnOcean®
Radio frequency 902 MHz (North America)
Transmission range Typically, 60 ft. (18.29 m) maximum from wireless adapter, assuming sensor and wireless adapter are separated by no more than 1 drop ceiling or 2 walls (drywall with metal studs)
Transmission interval Configurable in SensorBuilder. The sensor transmits:
• On change of sensed value, and
• At a regular interval (heartbeat). The default is every 15 minutes
Change of value threshold Configurable in SensorBuilder. The temperature must change by at least .288°F (.156°C) (the default) for the sensor to send a change of value
Minimum illumination strength 150 lux, constant
Degree of protection IP50
Operating environment 32° to 122°F (0° to 50°C) 5% to 95% relative humidity (non-condensing)
Housing ABS plastic, traffic white color
Weight 0.22 lb. (.10 kg)
Dimensions 3.7 in. W x 6.24 in. H x .79 in. D (9.4 cm W x 15.85 cm H x 2 cm D)
Compliance United States of America
FCC CFR 47, Chapter 1, Subchapter A, Part 15, Subpart B
Class B Contains FCC ID: SZV-STM300U
UL-916 (PAZX) Energy Management Equipment

Canada
Industry Canada Compliant, ICES-003, Class B
cUL Listed UL-916, PAZX7, Energy Management Equipment

Europe
EN50491-5-2:2009; Part 5-2: EMC requirements for HBES/BACS used in residential, commercial and light industry environment
EN50491-3:2009 Part 3: Electrical safety requirements for Home and Building Electronic Systems (HBES) and Building Automation and Control Systems (BACS)
Low Voltage Directive: 200695/EC RoHS Compliant: 2011/65/EU

Australia and New Zealand
C-Tick Mark AS/NZS 61000-6-3

Tingnan ang karagdagang mga detalye tungkol sa United Faith Sdn Bhd
United Faith Sdn Bhd
United Faith Sdn Bhd Air Conditioner Parts Supplier Selangor, Air Cond Services Kuala Lumpur (KL), Refrigeration Tools Malaysia, Singapore ~ United Faith Sdn Bhd