TECHNICAL PARAMETERS | |
---|---|
Measurement accuracy: | ±0.2% FS |
Resolution of voltage input: | 13 bits (8192 levels) |
Resolution of current input: | 7900 levels |
Signal character at binary input: | from potential-less contact or two-state voltage signal |
Minimum pulse duration at binary input: | 500 ms (shorter pulses may not be recorded) |
Maximum frequency at binary input: | 0.5 Hz (i.e. maximum 5 pulses for 10 s) |
Power current through contact at binary input: | 3 uA (contact closed) |
Voltage accross open contact at binary input: | maximum 3.6 V |
Low voltage level at binary input: | 0 to +0.2 V (maximum current from the input 3 uA |
High voltage level at binary input: | +3.0 to +30 V (maximum current to the input 100 nA |
Data logging interval: | adjustable from 10s to 24hours |
Display refresh and alarm state refresh: | every 10 s |
Total memory capacity: | 32000 values (in non cyclic mode) |
Data logging modes: |
noncyclic – logging stops after filling the memory cyclic – after filling memory oldest data is overwritten by new |
Operation temperature range: | -30 to +70°C |
Real time clock: | year, leap year, month, day, hour, minute, second |
Built-in connector for input signals: | Canon 9 pins, male |
Dimensions without connectors: | 93x64x29mm |
Weight including battery: | 130g |
Power: | Lithium battery 3,6V, size AA |
Typical battery life in operation from -5 to +35°C: (if often operated outside of the above temperature range battery life can be reduced to 75%) |
6 years |
Battery life in continuous on-line mode with interval 1 minute: | 4 years |
Battery life in continuous on-line mode with interval 10 seconds: | 1 year |
Protection: | IP67 - protected against influence of temporary immersion into water |