LR5041 |
LR5042 |
LR5043 |
Measurement items |
DC voltage 1ch |
DC voltage 1ch |
DC voltage 1ch |
Measurement range |
-50.00 to 50.00 mV |
-5.000 to 5.000 V |
-50.00 to 50.00 V |
Accuracy |
±0.5 %rdg. ±5 dgt. |
Storage capacity |
Instantaneous value mode: 60,000 data, Statistical value mode: 15,000 data |
Recording interval |
1 to 30 sec., 1 to 60 min., 15 selections |
Recording modes |
Instantaneous recording: at every recording interval
Statistical value recording: Measure at one second intervals, and record the instantaneous, maximum, minimum, and average values within every recording interval |
Recording methods |
One-time recording: Stop recording when the memory capacity is full
Endless recording: Continue recording even when the memory capacity is full (old data is overwritten)
Start: Logger button operation or scheduled time
Stop: Logger button operation or scheduled time, or auto-stop when the memory capacity is full (at one-time recording) |
Other functions |
Pre-heat function (requires external power supply during use of function), Always backs up last recorded data; backs up recorded data and setting conditions when battery power is low; guarantees approx. 30 sec. of recording operation and clock while battery is replaced |
Waterproof and dust-proof |
IP54 (EN60529) (with connection cable connected, but not including cable tip) |
Interfaces |
Infrared optical communications with LR5091, LR5092-20 |
Power supply |
LR6 (AA) Alkaline battery ×1, Battery life: Approx. 2 years (Instantaneous recording, with 1-minute interval and auto power saving, at 20 °C), Approx. 2 months (Instantaneous recording, with 1-second interval at 20 °C) |
Dimensions and mass |
79 mm (3.11 in) W × 57 mm (2.246 in) H × 28 mm (1.10 in) D, 105 g (3.7 oz) |
Included accessories |
LR6 (AA) Alkaline battery (built-in internal) ×1, Connection cable LR9802 ×1, Instruction manual ×1, Operation guide ×1, Kickstand ×1 |