code: H6520
Temperature, humidity, CO2 level sensor with two output relays. Humidex reading.
Sensor H6520 is designed for online monitoring of temperature, relative humidity of air without aggressive substances. Other devices are controlled by two relay outputs.
High precision capacitive polymer sensor ensures excellent long term calibration stability and ultimate accuracy. Measured values are also converted to other humidity interpretation: dew point temperature, absolute humidity, specific humidity, mixing ratio and specific enthalpy.
The CO2 measurement is based on a 2-source, 2-beam process. CO2 measurement with long-term stability is guaranteed thanks to the proven non-dispersive infrared (NDIR) CO2 measurement cell. The unique patented auto-calibration procedure compensates for aging of the infrared source and guarantees high reliability, long term stability and eliminates the need of periodical recalibration in the field.
Included in delivery:
Transmitter is also equipped with three alarm LEDs:
Green LED shines - CO2 concentration 0 to 1000 ppm
Yellow LED shines - CO2 concentration 1001 to 1200 ppm
Red LED shines - CO2 concentration 1201 ppm and more
Technical parameters | Value |
---|---|
Output | Ethernet |
Measured Value | CO2 + Temperature + Relative Humidity |
Construction Type | Ambient Air |
Design | Industrial |
Temperature Measuring Range | -30 to 60 °C |
Relay Output | Yes |
Two-State Input | No |
Lcd Display | Yes |
PoE | No |
Range of CO2 concentration measurement | 0 to 2000ppm |
Accuracy of CO2 concentration measurement | ±(50ppm +2% from reading) at 25°C and 1013hPa |
Optional range of CO2 concentration measurement | 0 to 10000ppm ±(100ppm +5% from reading) at 25°C and 1013hPa |
Relative humidity range | 0 to 100% |
Accuracy of relative humidity measurement | ±2.5% relative humidity from 5 to 95% at 23°C |
Accuracy of temperature output | ±0.4°C |
Resolution | 0.1°C, 0.1%RH, 1ppm |
Measuring interval of temperature and relative humidity | 2s |
Measuring interval of CO2 | 15s |
Available temperature units | degrees Celsius, degrees Fahrenheit |
Computed values | humidex, dew point, absolute humidity, specific humidity, mixing ratio, specific enthalpy |
Accuracy and range of dew point temperature output - for more details see graphs in manual |
±1.5°C at ambient temperature T<25°C and RH>30% range -60 to +80°C |
Accuracy and range of absolute humidity output |
±1.5g/m3 at ambient temperature T < 25°C range 0 to 400g/m3 |
Accuracy and range of specific humidity output |
±2g/kg at ambient temperature T < 35°C range 0 to 550g/kg |
Accuracy and range of mixing ratio output |
±2g/kg at ambient temperature T < 35°C range 0 to 995g/kg |
Accuracy and range of specific enthalpy output |
±3kJ/kg at ambient temperature T < 25°C range: 0 to 995kJ/kg |
Temperature compensation of the humidity sensor | all temperature range |
Temperature operating range | -30 to +60°C |
IP protection | IP30 |
Number of relay outputs | 2 |
Maximum switching voltage, current and power of relay output | 50V, 2A, 60VA |
Audible alarm | built-in beeper - switchable |
LAN connection | RJ-45 connector, 10Base-T or 100Base-TX |
Communication protocols | WWW, ModbusTCP, SNMPv1, SOAP, XML |
Alarm protocols | E-mail (SMTP authentication is supported), SNMP Trap, Syslog |
Configuration | WWW interface, T-Sensor |
Power | 9 to 30Vdc, power consumption approximately 1W |
Power connector | co-axial, diameter 5.5 x 2.1mm |
Dimensions | 136 x 213 x 45mm (W x H x D), stem length 75mm |
Weight | approximately 340g |