The Tap Changer Analyzer & Winding Ohmmeter RMO40TT instrument is designed for winding resistance measurement of inductive objects, and for a tap changer analysis. The RMO40TT instrument is based on the state of the art technology, using the most advanced switch mode technology available today. The RMO40TT instrument is accurate (0,1%), powerful (up to 40 A) and lightweight. It generates a true DC ripple free current with automatically regulated measurement and discharging circuit.
The RMO40TT instrument can perform a simple, quick and reliable transformer on-load tap changer condition assessment. This instrument enables measurements of a winding resistance in every tap position, current ripple values (percentage of a current drop during a tap change) and transition times during the tap changes. Problems with a connection, contacts, and selector/diverter switch operation (tap change with interruption) can be detected with these measurements.
The RMO40TT instrument provides temperature measurement for the Heat Run test by using four dedicated temperature channels. It enables obtaining the Hot Spot temperature along with temperature and resistance graphs which represent the cooling process.
Lebih maklumat tentang Labmetrik Electrical Sdn Bhd