As part of Carrier’s wireless sensing line, wireless plus sensors are used to measure temperature & humidity in a space. Because there are no wires to run, they can be added to your building easily.
Wireless sensors work in conjunction with a wireless adapter, which enables wireless communication between the sensors and an i-Vu® BACnet controller in the space. By sensing temperature, humidity and occupancy wirelessly, our i-Vu controllers can make smart decisions to optimize the control of heating, cooling, and lighting systems in the building, providing optimum occupant comfort and energy efficiency.
Power supply | Solar harvesting, internal energy storage |
Supplemental battery | A 1/2 AA 3.6 V 1200 mA battery is included to supplement power during commissioning and for low-light conditions |
Maximum operating life | Up to 5 days with no light power or battery |
Time to fully charge | Depends on available lux. Full charge in 8 hours @ 1000 lux or 24 hours @333 lux |
Temperature sensor measuring range | 32° to 104°F (0° to 40°C) |
Humidity sensor | 11% to 89%, ±3% RH typical |
Motion sensor | Panasonic AMN42122 - Effective detection range: 16.4 ft. (5 m) maximum |
Protocol | Customized version of EnOcean® |
Radio frequency | 902 MHz (North America) |
Transmission range | Typically, 75-80 ft. (18.29 m) maximum from wireless adapter, assuming sensor and wireless adapter are separated by no more than 1 drop ceiling or 2 walls (drywall with metal studs) |
Transmission interval |
Configurable in SensorBuilder. The sensor transmits: • On change of sensed value, and • At a regular interval (heartbeat). The default is every 15 minutes |
Change of value threshold | Configurable in SensorBuilder. The temperature must change by at least .288°F (.156°C) (the default) for the sensor to send a change of value |
Minimum illumination strength | 150 lux, constant |
Degree of protection | IP50 |
Operating environment | 32° to 122°F (0° to 50°C) 5% to 95% relative humidity (non-condensing) |
Housing | ABS plastic, traffic white color |
Weight | 0.20 lb. (.08 kg) |
Dimensions | 3.555 in. W x 3.768 in. H x 0.840 in. D (9.030 cm W x 9.570 cm H x 2.134 cm D) |
Compliance |
United States of America FCC CFR 47, Chapter 1, Subchapter A, Part 15, Subpart B Class B Contains FCC ID: SZV-STM300U UL-916 (PAZX) Energy Management Equipment Canada Industry Canada Compliant, ICES-003, Class B cUL Listed UL-916, PAZX7, Energy Management Equipment Europe EN50491-5-2:2009; Part 5-2: EMC requirements for HBES/BACS used in residential, commercial and light industry environment EN50491-3:2009 Part 3: Electrical safety requirements for Home and Building Electronic Systems (HBES) and Building Automation and Control Systems (BACS) Low Voltage Directive: 200695/EC RoHS Compliant: 2011/65/EU Australia and New Zealand C-Tick Mark AS/NZS 61000-6-3 |