As part of Carrier’s wireless sensing line, wireless Pro-F sensors are used to measure temperature, humidity and occupancy in a space. Because there are no wires to run, they can be added to your building easily.
Wireless sensors work in conjunction with a wireless adapter, which enables wireless communication between the sensors and an i-Vu® BACnet controller in the space. By sensing temperature, humidity and occupancy wirelessly, our i-Vu controllers can make smart decisions to optimize the control of heating, cooling, and lighting systems in the building, providing optimum occupant comfort and energy efficiency.
Power supply | Solar harvesting, internal energy storage |
Supplemental battery | Two SAFT LS-14500 AA 3.6V batteries. Not user replaceable. Under normal conditions, life expectancy is 5 to 10 years |
Maximum operating life | Up to 4 days with no light power or battery |
Time to fully charge | Depends on available lux. Full charge in 8 hours @ 1000 lux or 24 hours @333 lux |
Temperature sensor measuring range | 32° to 104°F (0° to 40°C) |
Humidity sensor | 0% to 100%, ±3% RH typical 5% drift per year |
Motion sensor | Panasonic AMN42122 - Effective detection range: 16.4 ft. (5 m) maximum |
Protocol | Customized version of EnOcean® |
Radio frequency | 902 MHz (North America) |
Transmission range | Typically, 60 ft. (18.29 m) maximum from wireless adapter, assuming sensor and wireless adapter are separated by no more than 1 drop ceiling or 2 walls (drywall with metal studs) |
Transmission interval |
Configurable in SensorBuilder. The sensor transmits: • On change of sensed value, and • At a regular interval (heartbeat). The default is every 15 minutes |
Change of value threshold | Configurable in SensorBuilder. The temperature must change by at least .288°F (.156°C) (the default) for the sensor to send a change of value |
Minimum illumination strength | 150 lux, constant |
Degree of protection | IP50 |
Operating environment | 32° to 122°F (0° to 50°C) 5% to 95% relative humidity (non-condensing) |
Housing | ABS plastic, traffic white color |
Weight | 0.22 lb. (.10 kg) |
Dimensions | 3.7 in. W x 6.24 in. H x .79 in. D (9.4 cm W x 15.85 cm H x 2 cm D) |
Compliance |
United States of America FCC CFR 47, Chapter 1, Subchapter A, Part 15, Subpart B Class B Contains FCC ID: SZV-STM300U UL-916 (PAZX) Energy Management Equipment Canada Industry Canada Compliant, ICES-003, Class B cUL Listed UL-916, PAZX7, Energy Management Equipment Europe EN50491-5-2:2009; Part 5-2: EMC requirements for HBES/BACS used in residential, commercial and light industry environment EN50491-3:2009 Part 3: Electrical safety requirements for Home and Building Electronic Systems (HBES) and Building Automation and Control Systems (BACS) Low Voltage Directive: 200695/EC RoHS Compliant: 2011/65/EU Australia and New Zealand C-Tick Mark AS/NZS 61000-6-3 |