The PremierLink Controller is an intelligent HVAC controls device that continuously monitors and regulates unit operation with reliability and precision that minimizes downtime to ensure maximum occupant comfort.
The PremierLink controller is compatible with the Carrier Comfort Network (CCN). Carrier's diagnostic standard tier display tools such as Navigator or Scrolling Marque can be used with the PremierLink controller.
User interfaces include the CCN Service Tool, ComfortVIEW™ and ComfortWORKS® software. When used as part of the CCN, other devices such as the CCN data transfer, Linkage Thermostat, or Comfort Controller can read data from or write data to the retrofit controller.
The PremierLink™ controller is designed to allow a service person or building owner to configure and operate the unit through the CCN user interface. A user interface is not required for day-to-day operation. All maintenance, configuration, setup, and diagnostic information is available through the Level II communications port to allow data access by an attached computer running Network Service Tool, ComfortVIEW™, or ComfortWORKS® software. Data access also can be obtained from System Pilot™ or Touch Pilot™ devices.
Field wiring is 18 to 22 AWG (American Wire Gage). The PremierLink controller is a NEC (National Electrical Code) Class 2 rated device.
2-wire, 24 VAC ± 15% at 40 va, 60 Hz
Normal operating supply range is 18 to 32 VAC with minimum consumption of 10 VA
Internal flash memory of 64K
The PremierLink controller space temperature range is –40 to 245 F (–40 to 118 C). The PremierLink controller has an allowable control set point range from 40 to 90 F (4 to 32 C) for heating and 45 to 99 F (7 to 37 C) for cooling.
The number of PremierLink controllers is limited only by the maximum number of controllers allowed on a CCN system. Bus length may not exceed 4000 ft (1219 m), with no more than 60 devices on any 1000 ft (305 m) section. Optically isolated RS-485 repeaters are required every 1000 ft (305 m). Status and control data is transmitted at a baud rate of between 9600 and 38.4K.
Two activity indicators present on the PremierLink controller indicate activity. A green LED will indicate activity on the communication port and a red LED will indicate status of processor operation.
Height: 53/4-in. (146 mm)
Width: 81/2-in. (216 mm)
Depth: 3-in. (76 mm)
Height: 7-in. (178 mm)
Width: 9-in. (229 mm)
Depth: 4-in. (102 mm)
Operating Temperature: –40 to 158 F (–40 to 70 C) at 10 to 95% RH (non-condensing)
Storage Temperature: –40 to 185 F (–40 to 85 C) at 10 to 95% RH (non-condensing)
Performance vibration: all planes/directions, 1.5G at 20 to 300 Hz
Operation: all planes/directions, 5G peak, 11 ms
Storage: all planes/directions, 100G peak, 11 ms
Office environment. Indoor use only.
Listed under UL 873, UL94-V0/5VB (plastic), and UL, Canada.
CE Mark, ASHRAE 90 and ASHRAE 62-99 compliant.
NOTE: Compliance standards subject to change without notice.