i-Vu® UV Open OPN-UV

i-Vu® UV Open OPN-UV

Kategori: Carrier Tersedia
Untuk maklumat lanjut, lawati laman web rasmi kami di unitedfaith.com.my

Penerangan

Product Integrated Controller

Integrated controller for unit ventilators capable of stand-alone operation or integrated with Carrier’s or any building automation system using BACnet®, Modbus® or Lonworks® protocol.

Carrier’s Unit Vent Open controller is an integrated component of a Carrier unit ventilator. The Unit Vent Open controller continuously monitors and regulates unit ventilator operation with reliability and precision. This advanced controller features a sophisticated, factory engineered control program that provides optimum performance and energy efficiency.

For added flexibility, the Unit Vent Open controller is capable of stand-alone operation, or it can be integrated with any Building Automation System utilizing the BACnet protocol.


carrier-bacnet-international-member
carrier-bacnet-testing-laboratories

Application Features

System Benefits

Hardware Features

BACNet Support Advanced application controller (B-AAC), as defined in BACNet 135-2001 Annex L
Communication Ports Network Port: EIA-495 port for BACnet MS/TP communications (baud rate is SIP switch selectable)
Comm Option port: For connecting a LON Option Card (future)
Local Access port: For system start-up and troubleshooting (115.2 kbps)
Rnet port: For connecting Carrier communicating room sensors and Carrier's touchscreen user interface
Inputs 2 binary inputs: Remote Occupancy Contact/Fan Status and Low Limit Thermostat
4 analog inputs: RAT (10k thermistor), SAT (10k thermistor), OAT (10k thermistor) and Changeover Switch (dry contact)/changeover sensor (10k thermistor). AIs have 10 bit A/D resolution.
Outputs 5 binary outputs: High speed fan, Medium Speed Fan (or Stage 3 Electric Heat), Low Speed Fan (or Stage 2 Electric Heat), 2-Pipe Valve/Heating Valve/Electric Heat Stage 1, and Cooling Valve/Electric Heat Stage 1 with 2-Pipe Electric Heat. Relay contacts rated at 1 A max. @ 24VAC/VDC, configured normally open.
3 analog outputs: Mixed Air Damper, Two-Pipe/Heating Valve/F&B Damper, and Cooling Valve. AOs rated at 0-10VDC 5mA max with 8 bit D/A resolution using filtered PWM.
Protection Incoming power and network connections are protected by non-replaceable internal solidstate polyswitches that reset themselves when the condition that causes a fault returns to normal. The power, network, input, and output connections are also protected.
Real Time Clock Battery-backed real time clock keeps track of time in event of power failure against voltage transient and surge events.
Battery 10-year Lithium CR2032 battery provides a minimum of 10,000 hours of trend data & time retention during power outages.
Status Indicators LED status indicators for communications, run status, error, power, and all digital outputs.
Controller Addressing Rotary DIP switches set BACnet MS/TP MAC address of controller.
Listed By UL-916 (PAZX), cUL-916 (PAZX7), FCC Part 15-Subpart B-Class A, CE EN50082-1997
Environmental Operating Range Operating: 0° to 140°F (-18° to 54°C), 10-90% relative humidity, non-condensing
Storage: -24°F to 140°F (-30° to 60°C), 10-90% relative humidity, non-condensing
Power Requirements 24VAC +/- 10%, 50-60Hz
18VA power consumption
26VDC (25V min, 30V max
Single Class 2 source only, 100VA or less

Lebih maklumat tentang United Faith Sdn Bhd
United Faith Sdn Bhd
United Faith Sdn Bhd Air Conditioner Parts Supplier Selangor, Air Cond Services Kuala Lumpur (KL), Refrigeration Tools Malaysia, Singapore ~ United Faith Sdn Bhd