Penerangan
Heat Pump Units with Puron® (R-410A) Refrigerant
6 to 20 Nominal Tons
WeatherMaker® 50TCQ rooftop units were designed to be easy to install, maintain, and operate, with customer-requested features including a gage port, centralized control center, plug-and-play accessory board, ''no-strip screw'' collars, and hinged access panels. Units are field-convertible to horizontal airflow without special adapter curbs or kits, making it easy for the installer to adjust to unexpected jobsite complications. Units are pre-wired and pre-charged with environmentally sound Puron (R-410A) refrigerant and are factory tested.
Performance Features
-
ASHRAE 90.1 compliant
-
Single-stage capacity control (sizes 04 to 07)
-
Two-stage cooling capacity control (sizes 08 to 24)
-
Up to 13.4 SEER, 12.2 IEER, 11.2 EER, HSPF 7.7, and COP 3.4
-
Cooling operating range up to 115 °F (46°C) and down to 25°F (-4°C) using winter start kit
-
Innovative non-corrosive composite condensate pan in accordance with ASHRAE 62 Standard, sloping design; side or center drain
-
Pre-painted exterior panels and primer-coated interior panels tested to 500 hours salt spray protection
Maintenance Features
-
Control terminal board facilitating simple safety circuit troubleshooting and simplified control box arrangement
-
Access panels with easy grip handles
-
Innovative, easy starting, no-strip screw feature on unit access panels
-
Belt drive evaporator-fan motor and pulley combinations available to meet any application
-
Electric drive X13 (5 speed/torque) motor (sizes 04 to 06)
-
Two-inch disposable return air filters
Installation Features
-
Same footprint as installed Carrier 3-12.5 ton rooftops back to 1989, reducing installation costs and time
-
Field convertible from vertical to horizontal airflow for slab mounting (sizes 04-14)
-
Provisions for thru-the-bottom power entry capability as standard
-
Single point electric and controls connections
-
Full perimeter base rail with built-in rigging adapters and fork truck slots
-
Dedicated vertical and horizontal airflow models available (sizes 17 to 28 only)
Reliability Features
-
Scroll compressors with internal line-break overload protection
-
Compressor crankcase heaters (sizes 05 to 24)
-
24-volt control circuit protected with resettable circuit breaker
-
Permanently lubricated evaporator-fan motor
-
Totally enclosed condenser motors with permanently lubricated bearings
-
Loss of charge, freeze protection, and high-pressure switches
-
Dependable time/temperature defrost board and logic
Factory-Installed Options
-
Cabinet
-
Thru-the-base electrical or gas-line connections
-
Hinged access panels
-
Coil Options
-
Cu/Cu indoor and/or outdoor coils
-
Pre-coated outdoor coils
-
Premium, E-coated outdoor coils
-
Condenser Protection
-
Condenser coil hail guard (louvered design)
-
Controls
-
PremierLink DDC communicating controller
-
RTU OPEN multi-protocol controller
-
Smoke detector (supply and/or return air)
-
Economizers & Outdoor Air Dampers
-
EconoMi$er IV (for electro-mechanical controlled RTUs)
-
EconoMi$er X (for electro-mechanical controlled RTUs with CA Title 24 FDD)
-
EconoMi$er2 (for DDC controlled RTUs)
-
Ultra-low leak economizer dampers
-
Motorized 2 position outdoor-air damper
-
Manual outdoor-air damper (sizes 17-24)
-
Barometric relief
-
Power exhaust (sizes 17-24)
-
Economizer Sensors & IAQ Devices
-
Single dry bulb temperature sensors
-
Single enthalpy sensors
-
CO2 sensor (wall, duct, or unit mounted)
-
Indoor Motor & Drive
-
Multiple motor and drive packages
-
Staged Air Volume (SAV) Indoor Fan Speed System (sizes 08-30)
-
Power Options
-
Convenience outlet (powered)
-
Convenience outlet (unpowered)
-
Non-fused disconnect
Field-Installed Accessories
-
Cabinet
-
Thru-the-base electrical or gas-line connections
-
Condenser Protection
-
Condenser coil hail guard (louvered design)
-
Controls
-
Thermostats, temperature sensors, and subbases
-
PremierLink DDC communicating controller
-
RTU OPEN multi-protocol controller
-
Smoke detector (supply and/or return air) (sizes 17-24)
-
Time Guard II compressor delay control circuit
-
Filter status switch
-
Fan status switch
-
Economizers & Outdoor Air Dampers
-
EconoMi$er IV (for electro-mechanical controlled RTUs)
-
EconoMi$er X (for electro-mechanical controlled RTUs with CA Title 24 FDD)
-
EconoMi$er2 (for DDC controlled RTUs)
-
Ultra-low leak economizer dampers
-
Motorized 2 position outdoor-air damper
-
Manual outdoor-air damper
-
Barometric relief
-
Power exhaust
-
Economizer Sensors & IAQ Devices
-
Single dry bulb temperature sensors
-
Differential dry bulb temperature sensors
-
Single enthalpy sensors
-
Differential enthalpy sensors
-
CO2 sensor (wall, duct, or unit mounted)
-
Electric Heat
-
Multiple Electric Resistance Heater KW Sizes
-
Single Point kit
-
Low Ambient Control
-
Winter start kit
-
Motormaster head pressure controller
-
Roof Curbs
-
Roof curb 14'' (356mm)
-
Roof curb 24'' (610mm)
Nominal Cooling Ton Size |
Cooling Stages |
AHRI Efficiency (SEER) EER |
Dimensions (in) LxWxH |
At 47°F |
At 17°F |
Unit Weight (lbs) |
Heating Capacity (Btuh) |
(HSPF) COP |
Heating Capacity (Btuh) |
(HSPF) COP |
6 |
1 |
11.1 |
74 x 47 x 41 |
67000 |
3.30 |
34800 |
2.25 |
630 |
7.5 |
2 |
11.2 |
88 x 59 x 49 |
86600 |
3.40 |
48000 |
2.25 |
885 |
8.5 |
2 |
11.2 |
88 x 59 x 49 |
96000 |
3.30 |
54500 |
2.25 |
910 |
10 |
2 |
11.0 |
88 x 59 x 49 |
116000 |
3.40 |
62300 |
2.25 |
1050 |
12.5 |
2 |
10.6 |
116 x 63 x 57 |
142000 |
3.20 |
76000 |
2.05 |
1370 |
15 |
2 |
10.8 |
128 x 87 x 49 |
166000 |
3.30 |
103000 |
2.40 |
1775 |
20 |
2 |
10.5 |
141 x 87 x 49 |
220000 |
3.30 |
134000 |
2.30 |
2100 |
Lebih maklumat tentang United Faith Sdn Bhd