Penerangan
Feature:
- Face-to-face dimensions of the EN standard
- Superior durability
- Stable performance
- Valve leakage meets ANSI Class IV
- High reduction ratio (20:1)
Specifications
Features |
For steam, EN Standard |
Type |
Pilot operated piston type |
Specification |
Product type |
Pilot-operated type |
Nominal size |
15A (1/2") - 100A (4") |
Application |
Steam |
End connection |
EN PN16 flanged |
Inlet pressure |
0.1 - 1 MPa |
Reduced pressure |
0.05 - 0.9 MPa |
Reduced pressure |
90% or less of the inlet pressure(gauge pressure) |
Min. differential pressure |
0.05 MPa |
Max. pressure reduction ratio |
20 : 1 |
Working temperature |
Max. 220 degree(C) |
Valve seat leakage |
0.01% or less of rated flow |
Material |
Body |
Ductile cast iron |
Valve and valve seat |
Stainless steel |
Piston, cylinder |
Brass and Bronze |
Diaphragm |
Stainless steel |
Dimensions (mm) and Weights (kg)
Size |
L (mm) |
H (mm) |
Weight (kg) |
Cv value |
15A(1/2) |
150 |
291 |
8.0 |
1 |
20A(3/4) |
150 |
291 |
8.5 |
2.3 |
25A(1) |
160 |
300 |
10.0 |
4 |
32A(1-1/4) |
180 |
333 |
14.0 |
6.5 |
40A(1-1/2) |
200 |
333 |
15.5 |
9 |
50A(2) |
230 |
353 |
21.0 |
16 |
65A(2-1/2) |
290 |
357 |
30.0 |
25 |
80A(3) |
310 |
404 |
37.0 |
36 |
100A(4) |
350 |
450 |
57.0 |
64 |
About flow rate