A device that is designed to detect the presence of fire in the form of heat and consequently activate other systems and devices, such as fire suppression systems and fire alarm.
SPECIFICATION |
Model |
AH-0626-2 |
AH-0626-3 |
AH-0626-4 |
Alarm Contact |
N/A |
N/A |
0.8A @ 30V DC
0.4A @ 125V AC
|
Voltage Range |
12 ~ 30V DC |
Alarm Current @ 24 V DC 470Ω |
40mA |
40mA |
45mA |
Standby Current @ 24 V DC 470Ω |
70µA |
Thermal Setting |
60°C |
Ambient Temperature |
0°C ~ +37.8°C |
Material |
Fire-proof plastic |
Dimensions |
102mm (Dia.) x 46mm(H) |
Weight |
120g |
120g |
130g |
Color |
White |
ORDER INFORMATION |
AH-0626-2 |
2-wire |
AH-0626-3 |
3-wire with remote indicator input |
AH-0626-4 |
4-wire with relay output |
EFFECTIVE ALERT AREA |
Construction / Height |
Under 4M |
4M ~ 8M |
Fire-proof Building |
90m2 |
45m2 |
Ordinary Building |
50m2 |
30m2 |
|