Penerangan
The RP-2002 is a six-zone FACP for single and dual hazard agent releasing applications. The RP-2002 provides reliable fire detection, signaling and protection for commercial, indus- trial and institutional buildings requiring agent-based releasing.
SPECIFICATION |
Initiating Device Circuits |
6 Class B , programmable |
Output Circuits |
4 Class B, programmable; rated at 3 amp |
Discharge Timer |
Yes, adjustable pre-discharge, discharge and waterflow delay |
Dual Hazard Operation |
Yes |
Cross Zone/ Double Interlock Capability |
Yes |
Relays |
3 Form-C; programmable |
Annunciators |
Yes; up to 8 LCD Display: 80 character |
LCD Power |
7.0 amps total system power |
|
Lebih maklumat tentang GREEN SIMEX ENGINEERING SDN BHD