code: H3531
Humidity, temperature, humidex Ethernet sensor on cable with two relay outputs.
Humidex sensor H3531 is designed for online monitoring of temperature, relative humidity, humidex of air without aggressive substances. Three binary inputs to detection of two-states signals are the advantage. Other devices are controlled by two relay outputs.
High precision capacitive polymer sensor ensures excellent long term calibration stability and ultimate accuracy. Measured values are also converted to other humidity interpretation: dew point temperature, absolute humidity, specific humidity, mixing ratio and specific enthalpy.
The device is supplied with T+RH probe with 1m cable. Cable lengths 2m or 4m available optionally.
Included in delivery:
Technical parameters | Value |
---|---|
Output | Ethernet |
Measured Value | Temperature + Relative Humidity |
Construction Type | With T+RH Probe on Cable |
Design | Industrial |
Temperature Measuring Range | -30 to 105 °C |
Relay Output | Yes |
Two-State Input | Yes |
Lcd Display | Yes |
PoE | No |
Relative humidity range | 0 to 100% |
Accuracy of relative humidity measurement | ±2.5% relative humidity from 5 to 95% at 23°C |
Accuracy of temperature output | ±0.4°C |
Resolution | 0.1°C, 0.1%RH |
Measuring interval | 2s |
Available temperature units | degrees Celsius, degrees Fahrenheit |
Computed values | humidex, dew point, absolute humidity, specific humidity, mixing ratio, specific enthalpy |
Accuracy and range of dew point temperature output - for more details see graphs in manual |
±1.5°C at ambient temperature T<25°C and RH>30% range -60 to +80°C |
Accuracy and range of absolute humidity output |
±1.5g/m3 at ambient temperature T < 25°C range 0 to 400g/m3 |
Accuracy and range of specific humidity output |
±2g/kg at ambient temperature T < 35°C range 0 to 550g/kg |
Accuracy and range of mixing ratio output |
±2g/kg at ambient temperature T < 35°C range 0 to 995g/kg |
Accuracy and range of specific enthalpy output |
±3kJ/kg at ambient temperature T < 25°C range: 0 to 995kJ/kg |
Temperature compensation of the humidity sensor | all temperature range |
Temperature operating range | -30 to +80°C |
IP protection | IP40 |
Number of relay outputs | 2 |
Maximum switching voltage, current and power of relay output | 50V, 2A, 60VA |
Number of binary inputs | 3 |
Signal for binary inputs |
dry contact, open collector or two-state voltage signal. Inputs are not galvanically isolated. |
Minimum pulse length at binary input | 500ms |
Low voltage level at binary input | 0 to +0.5V |
High voltage level at binary input | +3.0 to +30V |
Audible alarm | built-in beeper - switchable |
LAN connection | RJ-45 connector, 10Base-T or 100Base-TX |
Communication protocols | WWW, ModbusTCP, SNMPv1, SOAP, XML |
Alarm protocols | E-mail (SMTP authentication is supported), SNMP Trap, Syslog |
Configuration | WWW interface, T-Sensor |
Temperature operating range of LCD display | readable to operating temperature +70°C, it is recommended to switch OFF the LCD over +70°C |
Filtering ability of sensor cover | 0.025mm - filter with stainless steel mesh |
Power | 9 to 30Vdc, maximum consumption 1W |
Power connector | co-axial, diameter 5.5 x 2.1mm |
Length of the probe cable | 1m, 2m or 4m optionally |
Dimensions | 136 x 159 x 45mm (W x H x D), probe length 88mm, probe diameter 18mm |
Weight | approximately 410g - 1m probe |