Technical Data
Technical parameters Output
Value Ethernet
Measured Value Temperature + Relative Humidity
Construction Type For External Probes
Design Industrial
Temperature Measuring Range -55 to 100 °C
Relay Output No
Two-State Input No
Lcd Display No PoE Yes
Accuracy with DSTR162/C, DSTGL40/C, DSTG8/C probe ±0.5°C from -10 to +80°C, else ±2°C
Accuracy with DSRH01, DSRH02, DSRH05 probe ±3.5% RH (10% – 90% RH) at 25°C, ±2°C
Measuring temperature range with DSTR162/C, DSTGL40/C probe -30 to +80°C
Measuring temperature range with DSTG8/C probe -50 to +100°C
Measuring relative humidity range with DSRH01, DSRH02, DSRH05 probe 0 to 100%RH (not condensing)
Measuring temperature range with DSRH01, DSRH02, DSRH05 probe 0 to +50°C Resolution 0.1°C, 0.1%RH
Measuring interval 2s
Supported units degrees Celsius, degrees Fahrenheit, percent of Relative humidity
Temperature operating range -20 to +60°C
IP protection IP30
LAN connection RJ-45 connector, 10Base-T or 100Base-TX
Communication protocols WWW, ModbusTCP, SNMPv1, SOAP, XML
Protocols for alarms E-mail, SNMP Trap, Syslog
Configuration T-Sensor, WWW
configuration Power
Power over Ethernet according to IEEE 802.3af or 5Vdc
Power connector co-axial, diameter 5.5 x 2.1 mm
Dimensions 88 x 74 x 39.5 mm (W x H x D)
Weight approximately 125g