Fluke 1623-2 GEO Earth Ground Tester

Fluke 1623-2 GEO Earth Ground Tester

Category: Earth Ground Tester Available
For more information, visit our official website at mobicon.my

Description

The Fluke 1623-2 GEO Earth Ground Tester offers data storage and download capabilities via USB port. World class accessories will simplify and speed up testing time.

Fluke 1623-2 GEO Earth Ground Tester Summary

Detailed Specifications
General
Display:1999 digit LCD Display with special symbols, digit height 25 mm, fluorescent backlight
User interface Instant measurement through TURN and START one button concept. The only operating elements are rotary switch and START button
Robust, water and dust resistant Instrument is designed for tough environmental conditions (rubber protective cover, IP56)
Memory Internal memory storage up to 1500 records accessible via USB port
Temperature Range
Operating temperature -10 °C to 50 °C (14 °F to 122 °F)
Storage temperature -30 °C to 60 °C (-22 °F to 140 °F)
Temperature coefficient ± 0.1 % of reading/°C <18 °C >28 °C
Intrinsic error Refers to the reference temperature range and is guaranteed for 1 year
Operating error Refers to the operating temperature range and is guaranteed for 1 year
Climatic class C1 (IEC 654-1), -5 °C to +45 °C (23° to +115° F), 5 % to 95 % RH
Protective type IP56 for case, IP40 for battery door according to EN60529
Safety Protection by double and/or reinforced insulation. max. 50 V to earth. IEC61010-1: Pollution degree 2
EMC (emission immunity) IEC61326-1: Portable
Quality system Developed, designed and manufactured according to DIN ISO 9001
External voltage V ext, max = 24 V (dc, ac < 400 Hz), measurement inhibited for higher values
V ext rejection > 120 dB (162⁄3, 50, 60, 400 Hz)
Measuring time Typical 6 seconds
Max. overload 250 V rms (pertains to misuse)
Auxiliary power 6 x 1.5 V Alkaline (type AA LR6)
Battery life span Typical > 3,000 measurements
Dimensions (WxHxD) 250 mm x 133 mm x 187 mm (9.75 in x 5.25 in x 7.35 in)
Weight 1.1 kg (2.43 lb) including batteries 
7.6 kg (16.8 lb) incl. accessories and batteries in carrying case
RA 3-Pole Ground Resistance Measurement (IEC 1557-5)
Switch position RA 3-pole
Resolution 0.001 Ω to 10 Ω
Measuring range 0.020 Ω to 19.99 kΩ
Accuracy ± (2 % rdg + 3 d)
Operating error ± (5 % rdg + 3 d)
Measuring Principle: Current and Voltage Measurement
Measuring voltage Vm = 48 V ac
Short-circuit current > 50 mA
Measure frequency 128 Hz
Probe resistance (RS) Max 100 kΩ
Auxiliary earth electrode resistance (RH) Max 100 kΩ
Additional error from RH and RS RH[kΩ]•••RS[kΩ]/RA[Ω]•••0.2 %
Monitoring of RS and RH with error indicator.
Automatic range selection.
Measurement is not performed if the current through the current clamp is too low.
RA 4-Pole Ground Resistance Measurement (IEC 1557-5)
Switch position RA 4-pole
Resolution 0.001 Ω to 10 Ω
Measuring range 0.020 Ω to 19.99 kΩ
Accuracy ± (2 % rdg + 3 d)
Operating error ± (5 % rdg + 3 d)
Measuring Principle: Current and voltage Measurement
Measuring voltage Vm = 48 V ac
Short-circuit current > 50 mA
Measure frequency 128 Hz
Probe resistance (RS +RES) Max 100 kΩ
Auxiliary earth electrode resistance (RH) Max 100 kΩ
Additional error from RH and RS RH[kΩ]•••RS[kΩ]/RA[Ω]•••0.2 %
Monitoring of RS and RH with error indicator.
Automatic range selection.
RA 3-Pole Selective Ground Resistance Measurement with Current Clamp (RA with Clamp )
Switch position RA 3-pole with clamp
Resolution 0.001 Ω to 10 Ω
Measuring range 0.020 Ω to 19.99 kΩ
Accuracy ± (7 % rdg + 3 d)
Operating error ± (10 % rdg + 5 d)

Measuring Principle: Current/Voltage Measurement (with External Current Clamp)

Measuring voltage Vm = 48 V ac
Short-circuit current > 50 mA
Measure frequency 128 Hz
Probe resistance (RS) Max 100 kΩ
Auxiliary earth electrode resistance (RH) Max 100 kΩ
Monitoring of RS and RH with error indicator.
Automatic range selection.
Measurement is not performed if the current through the current clamp is too low.
RA 4-Pole Selective Ground Resistance Measurement with Current Clamp (RA with Clamp )
Switch position RA 4-pole with clamp
Resolution 0.001 Ω to 10 Ω
Measuring range 0.020 Ω to 19.99 kΩ
Accuracy ± (7 % rdg + 3 d)
Operating error ± (10 % rdg + 5 d)
Measuring Principle: Current/Voltage Measurement (with External Current Clamp)
Measuring voltage Vm = 48 V ac
Short-circuit current > 50 mA
Measure frequency 128 Hz
Probe resistance (RS) Max 100 kΩ
Auxiliary earth electrode resistance (RH) Max 100 kΩ
Monitoring of RS and RH with error indicator.
Automatic range selection.
Measurement is not performed if the current through the current clamp is too low.
Stakeless Ground Loop Measurement (2 Clamps )
Switch position RA 4-pole 2 clamps
Resolution 0.001 Ω to 10 Ω
Measuring range 0.020 Ω to 19.99 kΩ
Accuracy ± (7 % rdg + 3 d)
Operating error ± (10 % rdg + 5 d)
Measuring Principle: Stakeless Measurement of Resistance in Closed Loops Using Two Current Transformers
Measuring voltage Vm = 48 V ac
Measure frequency 128 Hz
Noise current (IEXT) Max. IEXT = 10 A (ac) (RA < 20 Ω)
Max. IEXT = 2 A (ac) (RA > 20 Ω)
Automatic range selection.
The information regarding stakeless ground loop measurements is only valid when used in conjunction with the recommended current clamps at the minimum distance specified.
 

 

 

More detail about Mobicon - Remote Electronic Sdn Bhd
Mobicon - Remote Electronic Sdn Bhd
Mobicon - Remote Electronic Sdn Bhd Measuring Instruments Selangor, Soldering Iron & Switches Supply Kuala Lumpur (KL), Audio Equipment Supplier Malaysia ~ Mobicon - Remote Electronic Sdn Bhd
Contact Us flagMalaysia