AquaForce® High-Efficiency, Water-Cooled, Indoor Liquid Screw Chiller 30XW

AquaForce® High-Efficiency, Water-Cooled, Indoor Liquid Screw Chiller 30XW

Category: Carrier Available
For more information, visit our official website at unitedfaith.com.my

Description

with R-134a Refrigerant

150 to 400 Nominal Tons

The 30XW units are high-efficiency, indoor water-cooled chillers with a quiet, low-vibration design featuring screw compressors. The units have excellent part load efficiency and a compact footprint less than 48 in. wide, making them great replacement units.

Water-cooled chillers within the scope of the AHRI WCCL certification program are certified in accordance with the AHRI Water-Cooled Water-Chilling and Heat Pump Water-Heating Packages Certification Program, which is based on AHRI Standard 550/590 (I-P) and AHRI Standard 551/591 (SI). Certified units may be found in the AHRI Directory at www.ahridirectory.org.


carrier-AHRI-550-590-551-591_WCCL
carrier-iso-9001
carrier-intertek-ETL-listed-C-US

 

Performance Features

Reliability Features

Maintenance Features

Installation Features

30XW Unit Size Capacity Input Power (kW) Evaporator Flow Evaporator Pressure Drop Condenser Flow Condenser Pressure Drop
Tons Output (kW)   gpm L/s Ft of
Water
kPa gpm L/s Ft of
Water
kPa
150 160.2 563.3 104.7 383.1 24.2 11.1 33.2 491.4 31.0 14.7 43.9
175 170.2 598.4 110.2 407 25.7 12.4 37.1 521.3 32.9 16.4 49
185 178.2 627.3 119.7 426.8 26.9 13.5 40.4 549.6 34.7 18.1 51.4
200 191.2 672.3 123.6 457.4 28.9 15.3 45.7 585.6 36.9 20.3 60.7
225 222.8 783.4 146.5 532.9 33.6 12.0 35.9 684.1 43.2 14.9 44.5
250 241.2 848.1 151.6 577 36.4 13.8 41.2 735.6 46.4 17 53.2
260 245.1 861.8 165.2 586.2 37 14.2 42.4 755.4 47.7 17.8 50.8
275 262.9 924.4 167.9 628.9 39.7 16.2 48.4 803.6 50.7 20 59.8
300 285.7 1004.5 183.9 683.2 43.1 18.8 56.2 875.3 55.2 23.3 69.6
325 322.5 1133.9 204.4 771.2 48.7 15.5 46.3 984.5 62.1 11.8 35.3
350 343.2 1206.7 216.3 820.9 51.8 17.3 51.7 1047 66.1 13.3 39.8
375 364.6 1281.9 236 872 55 19.4 58 1117 70.5 15 44.8
400 385.2 1354.4 242.4 921.4 58.1 21.4 64 1175 74.1 16.5 49.3
30XW Unit Size Full Load Efficiency (kW/Ton) IPLV (kw/Ton)
150 0.6537 0.5399
175 0.6477 0.5379
185 0.6710 0.5454
200 0.6462 0.5389
225 0.6576 0.5358
250 0.6284 0.5248
260 0.6739 0.5451
275 0.6384 0.5329
300 0.6439 0.5383
325 0.6338 0.4724
350 0.6303 0.4716
375 0.6473 0.4757
400 0.6293 0.4723

AHRI = Air Conditioning, Heating and Refrigeration Institute
IPLV = Integrated Part Load Value
NOTES
1. Rated in accordance with AHRI Standard 550/590 at standard rating conditions.
2. Standard rating conditions are as follows:
Cooler Conditions:
Leaving Water Temperature: 44°F (6.7°C)
Flow: 2.4gpm per ton (0.043 L/s per kW)
Condenser Conditions:
Entering Water Temperature: 85°F (29.4°C)
Flow: 3.0gpm per ton (0.054 L/s per kW)
Fouling Factor (Cooler):
0.00010 hr x sq ft x °F per Btuh (0.000018m2 x K per W)
Fouling Factor (Condenser):
0.00025 hr x sq ft x °F per Btuh (0.000044m2 x K per W)
3. IPLV is a single number part load efficiency value calculated from using the efficiency values at 100%, 75%, 50%, and 25% of load when the chiller is operating in AHRI conditions.
4. All data in the above table was generated in Packaged Chiller Builder version 3.29. Please refer to the most current version of the Packaged Chiller Builder for the most up-to-date data.
5. Contact Carrier for custom ratings.


More detail about United Faith Sdn Bhd
United Faith Sdn Bhd
United Faith Sdn Bhd Air Conditioner Parts Supplier Selangor, Air Cond Services Kuala Lumpur (KL), Refrigeration Tools Malaysia, Singapore ~ United Faith Sdn Bhd
Contact Us flagMalaysia