Download File: https://www.cometsystem.com/pdf/m1440
code: M1440
Battery powered datalogger for external CO2 probe up to 10 000ppm or 50 000ppm and inputs for connecting up to three temperature and/or humidity probes.
Multilogger can be installed permanently to Ethernet network or work as portable device.
Included is traceable calibration certificate in accordance with EN ISO/IEC17025.
The Multilogger is a battery operated datalogger capable of measuring and recording sensor and electrical values through its inputs.
Datalogger can be connected to Ethernet. Then measured values can be viewed on a web browser, as well as stored and downloaded for later analysis.
TEMPERATURE SENSOR - external probe Pt1000 | |
Measuring range | -200 to +600 °C |
Accuracy |
±0.2 °C (-200 to +100 °C); <br>±0.2 % from reading from +100 to +600 °C |
Resolution | 0.1 °C |
TEMPERATURE+HUMIDITY SENSOR - external probe T+RH DIGI |
|
Measuring range | according to the connected probe Digi/M |
Accuracy | according to the connected probe Digi/M |
Resolution | 0.1 °C |
DEW POINT | |
Measuring range | according to the connected probe Digi/M |
Accuracy | according to the connected probe Digi/M |
Resolution | 0.1 °C |
CO2 SENSOR 10.000ppm (OPTIONALLY) | |
Measuring range | 0 to 10.000 ppm |
Accuracy |
100 ppm + 5% of the measured value at 23 °C a 1 013 hPa |
CO2 SENSOR 50.000ppm (OPTIONALLY) | |
Measuring range | 0 to 50.000ppm |
Accuracy |
< ±(1,5 % from full scale +2% from the measured value) |
Resolution | 1 ppm |
External probe cable length CO2 | 1, 2 or 4 meters |
GENERAL TECHNICAL DATA | |
Operating temperature | -10 to +60 °C |
Channels |
3x external temperature probe or connectable temperature+humidity probe, 1x external CO<sub>2</sub> sensor |
Counted values |
dew point, absolute humidity, specific humidity, mixing ratio, specific enthalpy |
Memory |
1 000 000 values (noncyclic record), 600 000 values (cyclic record) |
Recording interval | 1s to 24 hours |
Display and alarm refresh | each 10 s |
Recording mode |
noncyclic - data logging stops after filling the memory<br>cyclic - after filling memory oldest data is overwritten by new |
Available temperature units | degrees Celsius, degrees Fahrenheit |
Communication interface | Ethernet, USB, RS232 |
Ethernet communication protocols | WWW, SNMPv1, XML, DATALINK |
Alarm protocols | |
Power |
AC adapter 230Vac/5Vdc (neccessary for Ethernet interface) |
Battery life | 3 - 4 weeks |
Protection class | IP20 |
Dimensions (without connectors) | 178 x 95 x 37mm, without attached cables |
Weight (including batteries) | approx. 380 g |
Warranty | 3 years |