The RP-2002 is a six-zone FACP for single and dual hazard agent releasing applications. The RP-2002 provides reliable fire detection, signaling and protection for commercial, indus- trial and institutional buildings requiring agent-based releasing.


SPECIFICATION
Initiating Device Circuits 6 Class B , programmable 
Output Circuits 4 Class B, programmable; rated at 3 amp 
Discharge Timer Yes, adjustable pre-discharge, discharge and waterflow delay 
Dual Hazard Operation Yes
Cross Zone/ Double Interlock Capability Yes 
Relays 3 Form-C; programmable
Annunciators Yes; up to 8 LCD Display: 80 character 
LCD Power 7.0 amps total system power