The Vacuum Circuit Breaker Analyzer 01 (VCBA 01) is Power Diagnostic Instrument Company’s state-of-the-art, field portable, light weight instrument designed for the comprehensive diagnostic testing of vacuum circuit breakers. The VCBA 01 can perform high voltage DC vacuum integrity tests as well as operating time tests on the circuit breaker main contacts.
The VCBA 01 applies a test voltage to the vacuum bottle arcing chamber for the time specified in the test settings. While the test voltage is applied to the vacuum circuit breaker arching chamber, the instrument monitors the leakage current to the ground. If the leakage current to the ground remains lower than the set limit, the instrument registers the test as successful. If the leakage current exceeds the set limit, the instrument shuts down and removes the test voltage from the arcing chamber and registers the test as a failed test.
Physical Specifications | Dimensions: 20''w x 9'' H x 17'' D (51 cm x 22 cm x 43 cm) Weight: 22 lbs. (9.9 Kg) |
Input Power | 90 – 240 Vac, 50/60 Hz |
Voltage Range | 10 kV – 80 kV DC in 1 kV steps |
Accuracy | 1.50% |
Output Voltage Ripple | 3% max |
Voltage Discharge Time | 3 seconds |
Leakage Current Setting | Up to 300 micro Amps, user selectable in 100 micro Amp steps |
CB Timing Test (optional feature) |
|
Dry Contact Inputs | 3 channels of CB main contacts |
Trigger Input Voltage Open/Close | 30 – 300 V, DC or peak AC |
Breaker Operations | Open, Close, Open-Close, Close-Open |
Timing Resolution | ±0.1 millisecond accuracy: 0.05% of reading ±1 ms |
User Interface |
|
Printer | Built-in 2'' wide thermal printer |
Display | Color touch-screen LCD (800 x 480 pixels) |
Keyboard | Full-sized ''QWERTY''-style industrial keyboard |
Safety |
|
Safety Switch | Hand-operated safety switch with 10 ft cable |
High Voltage Presence Indicators | Buzzer and LED high voltage presence indicators |
Operating/Storage Temperatures and Humidity |
|
Temperature | Operating: -10°C to +50°C (+15°F to +122°F) Storage: -30°C to +70°C (-22°F to +158°F) |
Humidity | 90% RH @ +40°C (+104°F) |
Data Storage and Analysis |
|
Internal Test Record Storage | Up to 100 timing and high voltage test records |
External Test Record Storage | USB Flash drive interface for test record storage and firmware updates (Flash drive not included) |
PC Software | Windows®-bases software is included with purchase price |