* Please refer to users manual for more detailed and up-to-date description of specification |
AC Watt (50 or 60 Hz, PF 0.5 to 1, CT=1) |
Range
|
Resolution
|
Accuracy of Readings
|
||
6800+6801 |
6800+6802 |
6800+3007
|
||
5.0 – 999.9W
|
0.1W
|
±1% ± 8dgts
|
±1% ± 8dgts
|
±1% of VA Range ±8dgts
|
1.000 – 9.999 KW
|
0.001 KW
|
±1% ± 8 dgts
|
±1% ± 8 dgts
|
±1% of VA Range ±8dgts
|
10.00 – 99.99 KW
|
0.01 KW
|
±1% ± 8 dgts
|
±1% ± 8 dgts
|
±1% of VA Range ±8dgts
|
100.0 – 999.9 KW
|
0.1 KW
|
±1% ± 8dgts
|
±1% ± 8dgts
|
±1% of VA Range ±8dgts
|
1000 – 9999 KW
|
1 KW
|
±1% ± 8dgts
|
±1% ± 8dgts
|
±1% of VA Range ±8dgts
|
0.000 – 9.999MW
|
0.001MW |
–
|
±1% ± 8 dgts
|
±1% of VA Range ±8dgts
|
AC Current( 50 or 60Hz, Auto Range,True RMS,Crest Factor<4,CT=1) |
Range
|
Resolution
|
Accuracy of Readings
|
|
6830+6801 (Overload Protection AC200A) |
0.050 – 9.999A
|
0.001A
|
±0.5% ± 5dgts
|
10.00 – 60.00A
|
0.01A
|
±0.5% ± 5dgts
|
|
60.00 – 99.99A
|
0.01A
|
±1.0% ± 5dgts
|
|
6830+6802 (Overload Protection AC2000A) |
0.04 – 10.00A
|
0.01A
|
–
|
0.4A – 100.0A
|
0.1A
|
±0.5% ± 5dgts
|
|
4.0 – 1000.0A
|
1A
|
±0.5% ± 5dgts
|
|
6830+3007
(Overload Protection AC3500A) |
4 – 300A
|
0.1A
|
±1% of Range ±5dgts
|
300.0 – 999.9A
|
0.1A
|
±1% of Range ±5dgts
|
|
1000 – 3000A
|
1A
|
±1% of Range ±5dgts
|
AC Voltage (50 or 60 Hz, Auto Range, True RMS, Crest Factor<4) |
Range
|
Resolution
|
Accuracy of Readings
|
Range
|
Resolution
|
Accuracy of Readings
|
4.0V – 500.0 (Phase to Neutral) |
0.1V |
± 0.5% ± 5dgts |
4.0V –600.0V (Phase to phase) |
0.1V |
± 0.5% ± 5dgts |
Harmonics of AC Voltage in % and in Magnitude (1 to 99th order, minimum voltage at the 50 or 60 Hz>AC 80V) |
Range
|
In Percentage
|
In Magnitude
|
||
Resolution
|
Accuracy of readings
|
Resolution
|
Accuracy of readings
|
|
1 – 20 th
|
0.1% |
±2%
|
0.1 V |
±2% ±0.5V
|
21 – 49 th
|
4% of reading ±2.0%
|
4% of reading ±0.5A
|
||
50 – 99 th
|
6% of reading ±2.0%
|
6% of reading ±0.5A
|
Harmonics of AC Current in % and in Magnitude Model 6830+6801(100A)(1 to 99th order, minimum current at 50 or 60 Hz is greater than 10% of the range) |
Range
|
In Percentage
|
In magnitude
|
||
Resolution
|
Accuracy of reading
|
Resolution
|
Accuracy of reading
|
|
1 – 10 th
|
0.1% |
±0.2 of reading ±1%
|
0.1mA / 0.1A
|
±0.2% of reading ±7dgts
|
11 – 20 th
|
±2% of reading ±1%
|
±2% of reading ±7dgts
|
||
2 1 – 50 th (A range)
|
±5% of reading ±1%
|
±5% of reading ±7dgts
|
||
2 1 – 50 th (mA range)
|
±10% of reading ±1%
|
±10% of reading ±7dgts
|
||
5 1 – 99 th
|
±35% of reading ±1%
|
±35% of reading ±7dgts
|
Model 6830+6802(1000A);6830+3007(3000A)(1 to 99th order, minimum current at the 50 or 60 Hz>20A) |
Range
|
In Percentage
|
In Magnitude
|
||
Resolution
|
Accuracy of reading
|
Resolution
|
Accuracy of reading
|
|
1 – 20 th
|
0.1%
|
±2%
|
0.1A(6802) / 0.3A(3007) |
±2% of reading ±0.4A/0.6A
|
21 – 49 th
|
4% of reading ±2.0%
|
±4% of reading ± 0.4A/0.6A
|
||
50 – 99 th
|
6% of reading ±2.0%
|
±6% of reading ± 0.4A/0.6A
|
Total Harmonic Distortion |
Range
|
Resolution
|
Accuracy(6801)
|
Accuracy(6802)
|
Accuracy(3007)
|
0.0 – 20%
|
0.1%
|
±1%
|
±2%
|
±2%
|
20 – 100%
|
0.1%
|
±3% of reading ±5%
|
±6% of reading ±1%
|
±6% of Range ±1%
|
100 – 999.9%
|
0.1%
|
±10% of reading ±10%
|
±10% of reading ±1%
|
±10% of Range ±1% |
Peak Value of Ac Voltage or AC Current ,VT=1 |
Range
|
Sampling Time
|
Accuracy of reading
|
50Hz
|
39 μS
|
±5% ±30digits
|
60Hz
|
33 μS
|
±5% ±30 digits
|
Crest Factor (C.F.) of ACV or ACA ,VT=1 |
Range
|
Resolution
|
Accuracy of reading
|
1.00 – 99.99
|
0.01
|
±5% ±30digits
|
Frequency in AUTO mode |
Range
|
Resolution
|
Accuracy of reading
|
45 – 65Hz
|
0.1Hz
|
0.1Hz
|
Power Factor (PF) |
Range
|
Resolution
|
Accuracy of reading
|
0.00 – 1.00
|
0.01
|
± 0.04
|
Phase Angle (Φ) |
Range
|
Resolution
|
Accuracy of reading
|
-180 。 to 180 。
|
0.1 。
|
± 1 。
|
Conductor Size (6801) | 30mm (approx) |
Conductor Size (6802) | 約55mm(approx.), 64 X 24mm(Bus Bar) |
Battery Type | 1.5V SUM-3 x 8 |
Display | Dot Matrix LCD with backlight |
Power Consumption | 140mA (approx.) |
External DC Input | DC 12V adaptor (for safety purpose, the adaptor must be certified with 600Visolation protection) |
LCD update rate | 1 times / sec |
No. Of Samples/Period | 1024 |
Operating Humidity | < 85% relative |
Operating Temperature | -10°C to 50°C |
Storage Humidity | < 75% relative |
Storage Temperature | - 20°C to 60°C |
Weight(6830) | 1160g |
Weight(6801) | 200g |
Weight(6802) | 600g |
Weight(3009) | 390g |
Weight(3007) | 410g |
Dimension(6830) | 257mm(L) x 155mm(W) x 57mm(H), 10.1'(L) x 6.1' (W) x 2.3' (H) |
Dimension(6801) | 210mm(L) x 62mm(W) x 36mm(H), 8.3 ' (L) x 2.5' (W) x 1.4' (H) |
Dimension(6802) | 244mm(L) x 97mm(W) x 46mm(H), 9.6 ' (L) x 3.8' (W) x 1.8' (H) |
Dimension(3009) | 130mm(L) x 80mm(W) x 43mm(H), 5.1 ' (L) x 3.1' (W) x 1.7' (H) |
Dimension(3007) | 130mm(L) x 80mm(W) x 43mm(H), 5.1 ' (L) x 3.1' (W) x 1.7' (H) |
Accessories | Test leads x 4,alligator clips x 4,Carrying bag x 1,Users manual x 1,Batteries 1.5V x 8 |