Specifications
- Power Supply: 24 VAC
- Current Consumption: 25 mA
- Output Signal: Depends on output configurations
- Out Put Ratings: - Triac output: 0.5 A maximum @ 24 VAC
- Analog output (SCR connection): 0 - 10 V, 10kΩ minimum
- Analog output (SSR connection): 0 - 10 V, 45 mA maximum
- Set Point Range: 50°F to 95°F (10°C to 35°C)
- Temperature Display: 32°F to 140°F(0°C to 60°C)
- Temperature Display Resolution: 1°F (0.5°C)
- Mode Hysteresis: 4°F (2°C)
- Automatic Changeover Deadband: 9°F (5°C)
- Duty Cycle: Depends on output configurations
- NSB Offset: Programmable 2°F to 18°F (1°C to 9°C)
- NSB Override Period: 2 Hours
- Memory Protection: Configuration and setpoint
- Temperature Control: Proportional integral adaptive (P.I.A.)
- Operating Temperature: 32°F to 140°F (0°C to 60°C)
- Storage Temperature: -4°F to 122°F (-20°C to 50°C)
Description
The TB6980/TB7980 digital thermostats provide proportional plus integral individual space temperature control in zoned commercial HVAC systems such as hydronic and pressure dependent VAV with or without reheat. There are four different models:
- TB7980A(singleoutput,modulating)
- TB6980A(singleoutput,floating)
- TB7980B (multiple output modulating)
- TB6980B (multiple output, floating)
Depending on the models, the thermostat can have up to three out- puts for the following applications:
Floating or Modulating damper/valve actuator control
Damper/valve actuator control with duct reheat and auxiliary heat (B models only)
Hydronic systems (room control, perimeter heating and cooling)
More detail about Coolinic Chiller Parts Center Sdn Bhd