The insulation meter is designed to simplify on-site troubleshooting in both industrial and solar installations. With selectable test voltages of 250 ... 2500 V and resistance measurement up to 200 GΩ can be carried out with a single tool thanks to this device. The intuitive user interface, short-circuit current of up to 1.8 mA, and CAT IV 600 V safety make these portable high-voltage insulation meters ideal for fast and stable resistance measurements anywhere.
The test voltage can be variably selected with 250 V, 500 V, 1000 V, 2000 V and 2500 V. In addition, it can also handle AC and DC voltages of 10 ... 600 V. The isolation meter has a memory for 100 data records, which can be called up via the LC display. In addition to the data hold function, the insulation meter offers the possibility to measure the Polarization Index (PI) and the Dielectric Absorption Ratio (DAR). These features are particularly useful for condition monitoring and maintenance of electrical insulation, as they help identify potential problems early on and extend the life of the equipment. A high-voltage indicator ensures safety during operation and a low-battery indicator indicates in good time that a battery change is necessary.
The instrument is particularly suitable for measuring insulation resistances on various electrical devices and insulation materials such as motors, cables, switches and other electrical components, making it ideal for maintenance, repair and testing work. With its modern design and stable performance, the device convinces in every respect. For easy storage and convenient transport, the insulation knife comes in a handy zippered bag.
DC voltage DC | |
Measuring range | 10 ... 600 V |
Resolution | 1 V |
Accuracy | ±(0.8% v.Mw. +5 digits) |
AC voltage AC | |
Measuring range | 10 ... 600 V |
Resolution | 1 V |
Accuracy | ±(1% v.Mw. +5 digits) |
Overload | 2000 V AC max. 1 minute |
Insulation resistance | |
Test voltage DC | 1000 V |
Measuring range | 1 M Ω ... 20 GΩ |
Resolution | 0.01 m Ω |
Accuracy | ±(5% v.Mw. +10 digits) |
Insulation resistance | |
Test voltage DC | 2500 V |
Measuring range | 5 m Ω ... 200 GΩ |
Resolution | 0.01 m Ω |
Accuracy | ±(5% v.Mw. +10 digits) |
General technical data | |
Measurement functions | HOLD, PI, DAR |
Display Type | LCD |
Display size | 3.7 inches |
Recording medium | Internal memory |
Storage capacity | 100 records |
Standard(s) | EN 61010-1 |
Automatic shut-off | 25 min |
Safety standard | CAT III 1000V , CAT IV 600 V |
Language | English (US) |
Protection class (device) | IP20 |
Weight | 651 g |
Service conditions | 0 ... 35 °C , 0 ... 75 % RH |
Storage | 0 ... 35 °C , 0 ... 75 % RH |
Battery/Battery | 8 x 1.5V AA Battery, Alkaline Manganese |
Capacity | 2500 mAh |
Dimensions ( L x W x H ) | 140 x 180 x 70 mm |