40UV - Vertical
40UH - Horizontal
Airstream unit ventilators meet the strict indoor air quality requirements of schools, hospitals, and institutions. The 40UV units are compact, efficient, and easy to install and maintain. Units are designed to provide economic, dependable long-term performance.
Unit 40UV, UH | 050* | 075 | 100 | 125 | 150 | 200† |
---|---|---|---|---|---|---|
Nominal Airflow (Cfm) | 500 | 750 | 1000 | 1250 | 1500 | 2000 |
Fans | ||||||
Quantity | 1 | 2 | 3 | 4 | 5 | 5 |
Diameter (in) | 8.32 | 8.32 | 8.32 | 8.32 | 8.32 | 9.5 |
Width (in) | 8 | 8 | 8 | 8 | 8 | 6 |
40UV Filters | ||||||
Nominal Size (in) (1 in. thick) | 9-1/4 x 24-1/4 | 9-1/4 x 36-1/4 | 9-1/4 x 48-1/4 | 9-1/4 x 60-1/4 | 9-1/4 x 72-1/4 | -- |
Nominal Size (in) (2 in. thick) | 9-1/4 x 24-1/4 | 9-1/4 x 36-1/4 | 9-1/4 x 48-1/4 | 9-1/4 x 60-1/4 | 9-1/4 x 72-1/4 | -- |
Quantity | 1 | 1 | 1 | 1 | 1 | -- |
40UH Filters | ||||||
Nominal Size (in) (1 in. thick) | -- | 9-1/4 x 36-1/4 | 9-1/4 x 48-1/4 | 9-1/4 x 60-1/4 | 9-1/4 x 72-1/4 | 9-1/4 x 72-1/4 |
Nominal Size (in) (2 in. thick) | -- | 9-1/4 x 36-1/4 | 9-1/4 x 48-1/4 | 9-1/4 x 60-1/4 | 9-1/4 x 72-1/4 | 9-1/4 x 72-1/4 |
Quantity | -- | 1 | 1 | 1 | 1 | 1 |
40UV Shipping Weight** (Approx lb) | ||||||
16-5/8 in Deep Unit | 330 | 400 | 480 | 590 | 660 | -- |
21-7/8 in Deep Unit | 340 | 410 | 490 | 605 | 675 | -- |
40UH Shipping Weight** (Approx lb) | ||||||
34 in Deep Unit | -- | 420 | 500 | 620 | 690 | -- |
39-1/2 in Deep Unit | -- | 500 | 600 | 740 | 830 | -- |
43-1/2 in Deep Unit | -- | 530 | 640 | 790 | 880 | 1020 |
47-1/2 in Deep Unit | -- | -- | -- | -- | -- | 1050 |
40UV Installed Weight** (Approx lb) | ||||||
16-5/8 in Deep Unit | 315 | 380 | 460 | 570 | 640 | -- |
21-7/8 in Deep Unit | 325 | 390 | 470 | 595 | 655 | -- |
40UH Installed Weight ** (Approx lb) | ||||||
34 in Deep Unit | -- | 405 | 580 | 600 | 670 | -- |
39-1/2 in Deep Unit | -- | 485 | 580 | 720 | 810 | -- |
43-1/2 in Deep Unit | -- | 515 | 620 | 770 | 860 | 1000 |
47-1/2 in Deep Unit | -- | -- | -- | -- | -- | 1030 |
Coil Water Weight (Approx lb per row of coil) | 1.0 | 1.5 | 2.0 | 2.4 | 2.7 | 2.7 |
Coil Connections (in OD) | Return | Supply | ||||
Water Coils with 1-5 Rows | 7/8 | 7/8 | ||||
Steam Coils (All Units) | 7/8 | 1-1/8 | ||||
Suction | Liquid | |||||
DX Coils | 7/8 | 3/8 | ||||
Condensate Drain | 7/8 |
DX = Direct Expansion
*40UV only.
†40UH 43-1/2 and 47-1/2 in. deep units only.