Even when the utmost care is taken, contaminants will be introduced as fuel is transported from the refinery to its point-of-use. Common contaminants, including pipe scale, silica, metal debris and water, can quickly deteriorate fuel cleanliness far beyond engine manufacturer’s minimum requirements for fuel cleanliness.
Velcon Aquacon® Diesel (AD) filters can remove both particulate and water contaminants in fuels to meet stringent downstream ISO 4406 and ASTM D975 cleanliness standards for both diesel or biodiesel fuels. The AD design incorporates multiple layers of both high efficiency long-life particulate retention and water absorbing media.
Tiered Ratings
- 2, 4 or 6 micron rated AD filters are excellent solutions for delivering fuel ready for dispensing while assuring both ISO 4406 and ASTM D975 cleanliness levels are consistently met. Each progressively tighter AD filter rating adds additional particle removal capability and lowers ISO 4406 particle counts
- The 10, 25 and 40 micron rated filters are ideal for managing fuel contamination entering and leaving terminal storage tanks throughout the fuel transfer process
Benefits
- More reliable fuel injector performance by reducing particulate which can cause cascading damages
- Reduced operating costs due to repair of equipment damaged by particulate and water contaminants
- Reduced engine maintenance due to fewer components being damaged by contaminants
- More efficient fuel consumption due to fewer inhibiting particulate and water contaminants
- Removes free aqueous contaminants from fuel
Water Absorbance Versus Water Coalescing
AD filters are designed to remove both water and particulates from either diesel or biodiesel fuels. AD filters are ideal for use in biodiesel and blended fuels where high levels of surfactants (glycerin) could disrupt water coalescing. When continual removal of water from petroleum based fuel is required, the application of coalescing technology is optimal or preferred.
Performance Characteristics | |
---|---|
Inside Diameter (inch) | 3, 3.5 |
Maximum Operating Temperature (C) | 65 |
Maximum Operating Temperature (F) | 150 |
Maximum Burst Pressure (psi) | 75 |
Maximum Burst Pressure (bar) | 5.2 |
Changeout Pressure Differential (PSI) | 25 |
Changeout Pressure Differential (Bar) | 1.7 |
pH Range (Continuous Operation) | 5 - 9 |
Brand | Velcon |
Flow Rate | Depends on fluid viscosity and application. See brochure for more information. |
Application | Diesel |
Filter Type | Water Absorber |